SECTION 7 – UNIT CONTROLS
S Y S
1
N O
S Y S
2
N O
This message informs the operator that the chilled
liquid temperature is below the point (determined by
the setpoint and control range) that the microprocessor
board will bring on a system or that the microprocessor
board has not loaded the lead system far enough into
the loading sequence to be ready to bring the lag system
"ON". The lag system will display this message until the
loading sequence is ready for the lag system to start.
S Y S
1
C O M P S
S Y S
2
C O M P S
The COMPS RUNNING message indicates that the
respective system is running due to demand. The "X"
will be replaced with the number of compressors in that
system that are running.
S Y S
1
A R
S Y S
2
A R
The anti-recycle timer message shows the amount of
time left on the respective systems anti-recycle timer.
This message is displayed when the system is unable to
start due the anti-recycle timer being active.
S Y S
1
A C
S Y S
2
A C
The anti-coincidence timer is a software feature that
guards against two systems starting simultaneously.
This assures instantaneous starting current does not
become excessively high due to simultaneous starts.
The microprocessor board limits the time between
compressor starts to one minute regardless of demand
or the anti-recycle timer being timed out. The anti-
coincidence timer is only present on two system units.
S Y S
1
D S C H
S Y S
2
D S C H
When this message appears, discharge pressure limiting
is in effect. The Discharge Pressure Limiting feature
is integral to the standard software control; however
the discharge transducer is optional on some models.
Therefore, it is important to keep in mind that this
control will not function unless the discharge transducer
is installed in the system.
140
C O O L
L O A D
C O O L
L O A D
R U N
X
R U N
X
T I M E R
X X
S
T I M E R
X X
S
T I M E R
X X
S
T I M E R
X X
S
L I M I T I N G
L I M I T I N G
The limiting pressure is a factory set limit to keep the
system from faulting on the high discharge pressure
cutout due to high load or pull down conditions. When
the unload point is reached, the microprocessor board
will automatically unload the affected system by de-
energizing one compressor. The discharge pressure
unload will occur when the discharge pressure gets
within 10 PSIG (0.69 barg) of the programmed discharge
pressure cutout. This will only happen if the system is
fully loaded and will shut only one compressor off. If
the system is not fully loaded, discharge limiting will
not go into effect. Reloading the affected system will
occur when the discharge pressure drops to 85% of the
unload pressure and 10 minutes have elapsed.
S Y S
1
S U C T
S Y S
2
S U C T
When this message appears, suction pressure limiting is
in effect. The suction pressure limit is a control point that
limits the loading of a system when the suction pressure
drops to within 15% above the suction pressure cutout.
On a standard system programmed for 44 PSIG/3.0 Bar
suction pressure cutout, the microprocessor board would
inhibit loading of the affected system with the suction
pressure less than or equal to 1.15 x 44 PSIG/3.0 Bar
= 50 PSIG/3.5 Bar. The system will be allowed to load
after 60 seconds and after the suction pressure rises
above the suction pressure load limit point.
S Y S
1
L O A D
S Y S
2
L O A D
This message indicates that load limiting is in effect and
the percentage of the limiting in effect. This limiting
could be due to the load limit/pwm input, ISN or RCC
controller sending a load limit command.
M A N U A L
O V E R R I D E
If MANUAL OVERRIDE mode is selected, the STATUS
display will show this message. This will indicate that
the Daily Schedule is being ignored and the chiller
will start-up when chilled liquid temperature allows
(Remote Contacts, UNIT switch and SYSTEM switches
permitting). This is a priority message and cannot be
overridden by anti-recycle messages, fault messages, etc.
when in the STATUS display mode. Therefore, do not
expect to see any other STATUS messages when in the
MANUAL OVERRIDE mode. MANUAL OVERRIDE
is only to be used in emergencies or for servicing. Manual
override mode automatically disables itself after 30
minutes.
FORM 150.72-NM3 (1020)
ISSUE DATE 10/05/2020