Fig. 47 - Dimensions (English) Ylaa0440He - York YLAA0285SE Manual

Air-cooled scroll chillers with microchannel condenser coils style a (50 hz) 57 - 142 ton
Table of Contents

Advertisement

FORM 150.72-NM3 (1020)
ISSUE DATE 10/05/2020
DIMENSIONS - YLAA0440HE (ENGLISH)
14012
POWER ENTRY
8712 WIDE X 178 HIGH
VIEW B-B
BOTTOM OF PANEL
B
749
TO CLR CONN
2242 BASE WIDTH
2261
FRONT VIEW
POWER: SINGLE POINT SUPPLY WITH TERMINAL BLOCK
NOTE:
Placement on a level surface of free of obstructions
(including snow, for winter operation) or air circulation
ensures rated performance, reliable operation, and ease
of maintenance. Site restrictions may compromise
minimum clearances indicated below, resulting in
unpredictable airflow patterns and possible diminished
performance. Johnson Controls's unit controls will
optimize operation without nuisance high-pressure
FIG. 47 – DIMENSIONS (ENGLISH) YLAA0440HE
JOHNSON CONTROLS
525
2077
79
ORIGIN
Y
C G
(WATER
INLET)
B
2389
1086
5/8" DIA MOUNTING
HOLES(TYP)
0
0
0
0
193
1753
TOP VIEW
X
8"
(3) RIGGING HOLES
562
EACH SIDE
588
1473
safety cutouts; however, the system designer must
consider potential performance degradation. Access to
the unit control center assumes the unit is no higher than
on spring isolators. Recommended minimum clearances:
Side to wall – 6'; rear to wall – 6'; control panel to end
wall – 4'0''; top – no obstructions allowed; distance
between adjacent units – 10'. No more than one adjacent
wall may be higher than the unit.
SECTION 5 – TECHNICAL DATA
0
0
2032
1578
1675
4731
RIGHT VIEW
28 (TYP)
5 5
8"
(WATER
OUTLET)
2X 438
117