Fig. 43 - Dimensions (English) Ylaa0300He,Ylaa0360Se, Ylaa0400Se - York YLAA0285SE Manual

Air-cooled scroll chillers with microchannel condenser coils style a (50 hz) 57 - 142 ton
Table of Contents

Advertisement

FORM 150.72-NM3 (1020)
ISSUE DATE 10/05/2020
DIMENSIONS - YLAA0300HE,YLAA0360SE, YLAA0400SE (ENGLISH)
14012
POWER ENTRY
8712 WIDE X 178 HIGH
VIEW B-B
BOTOM OF PANEL
B
780
TO CLR CONN
2242 BASE WIDTH
2261
FRONT VIEW
POWER: SINGLE POINT SUPPLY WITH TERMINAL BLOCK
NOTE:
Placement on a level surface of free of obstructions
(including snow, for winter operation) or air circulation
ensures rated performance, reliable operation, and ease
of maintenance. Site restrictions may compromise
minimum clearances indicated below, resulting in
unpredictable airflow patterns and possible diminished
performance. Johnson Controls's unit controls will
optimize operation without nuisance high-pressure
FIG. 43 – DIMENSIONS (ENGLISH) YLAA0300HE,YLAA0360SE, YLAA0400SE
JOHNSON CONTROLS
525
79
ORIGIN
2393
B
5/8" DIA MOUNTING
HOLES(TYP)
2077
2977
193
Y
TOP VIEW
X
C G
6"
(WATER
INLET)
1086
(2) RIGGING HOLES
473
EACH SIDE
588
RIGHT VIEW
safety cutouts; however, the system designer must
consider potential performance degradation. Access to
the unit control center assumes the unit is no higher than
on spring isolators. Recommended minimum clearances:
Side to wall – 6'; rear to wall – 6'; control panel to end
wall – 4'0''; top – no obstructions allowed; distance
between adjacent units – 10'. No more than one adjacent
wall may be higher than the unit.
SECTION 5 – TECHNICAL DATA
28 (TYP)
6"
(WATER OUTLET)
588
981
3613
5 5
2X 381
113

Hide quick links:

Advertisement

Table of Contents
loading