Technical data
Table 8 Measurement performance
Property
Carbon dioxide
Measurement range
Accuracy across temperature range
+20 ... +30 °C (+68 ... +86 °F)
+10 ... +20 °C (+50 ... +68 °F), +30 ... +40 °C
(+86 ... +104 °F)
+0 ... +10 °C (+32 ... +50 °F), +40 ... +50 °C
(+104 ... +122 °F)
Stability in typical HVAC applications
Warm-up time
Response time (63 %)
Carbon dioxide sensor
Product lifetime
Table 9 Operating environment
Property
Operating temperature
Operating humidity
Storage temperature
EMC compliance
Table 10 Inputs and outputs
Property
Supply voltage
Max. current consumption at 18 VDC
Max. power consumption at 30 VAC
Specification
0 ... 5000 ppm
±(30 ppm +3 % of reading)
±(35 ppm +3.7 % of reading)
±(40 ppm +4.8 % of reading)
±(15 ppm + 2 % of reading) over five years
10 min for full specification
7 min
Vaisala CARBOCAPâ GM10
> 15 years
Specification
0 ... +50 °C (+32 ... +122 °F)
0 ... 95 %RH
Dew point < 30 °C (+86 °F)
−40 ... +70 °C (−40 ... +158 °F)
EN61326-1, Industrial environment
Specification
18 ... 35 VDC
24 VAC ±20 % 50/60 Hz
45 mA
1 W
13