Page 1
AIR-COOLED SCREW LIQUID CHILLERS New Release Form 201.19-NM8 (804) INSTALLATION, OPERATION & MAIN TE NANCE 035-20886-000 YCAS AIR-COOLED LIQUID CHILLERS YCAS0685EB THROUGH YCAS0965EB (3 COMPRESSOR) YCAS1065EB THROUGH YCAS1215EB (4 COMPRESSOR) STYLE G R407C 50 Hz 00258VIP (YCAS 4 SYSTEM EPROMs) (YCAS 3 SYSTEM EPROMs) MICROPROCESSOR BOARD MICROPROCESSOR BOARD...
Page 2
While YORK makes no com mit ment to update or provide current information au to mat i cal ly to the manual owner, that information, if ap pli ca ble, can be ob tained by con tact ing the nearest YORK Engineered Systems Service offi...
Page 3
YORK’s pub lished spec i fi ca tions and must be per formed ONLY by qual i fi ed YORK personnel. YORK will not be re spon si ble for dam ag es/problems re sult ing from im prop er con nec tions to the con trols or ap pli ca tion of im prop er con trol sig nals.
Remote Run / Stop............33 Building Automation System (BAS) Interface....21 Remote Print..............33 Condenser Coil Protection ..........21 Remote Setpoint Offset – Temperature .......33 DX EVAPORATOR AND STARTER OPTIONS ..22 Remote Setpoint Offset – Current .......33 UNIT ENCLOSURE OPTIONS......... 22 YORK INTERNATIONAL...
Page 5
1.9 Motor Protector Modules ........138 PHYSICAL DATA - YCAS R-407C (SI UNITS) ..48 1.10 Ems/bas Controls..........140 OPERATING LIMITATIONS AND SOUND POWER 1.11 Microprocessor Board Layout ......142 DATA................. 49 1.12 Logic Section Layout ........143 ELECTRICAL DATA..........50 1.13 Anti-recycle Timer..........144 YORK INTERNATIONAL...
Page 6
4.6 Fault History Data – Local Display Messages ..164 SECTION 11 - TROUBLESHOOTING 4.7 Fault History Data – Remote Printout ....168 GUIDE ........212 LIMITED WARRANTY YORK AMERICAS 5. ENTRY KEYS............169 ENGINEERED SYSTEMS........214 5.1 General ..............169 WARRANTY ON NEW EQUIPMENT ..... 214 5.2 Numerical Keypad..........169...
Page 7
TABLE 15 - DIGITAL INPUTS........ 199 TABLE 16 - ANALOG OUTPUTS ......199 TABLE 17 – ISN RECEIVED DATA ....... 201 TABLE 18 – ISN TRANSMITTED DATA ....201 TABLE 19 – ISN OPERATIONAL AND FAULT CODES........204 YORK INTERNATIONAL...
Page 8
FIG. 33 – CONNECTION DIAGRAM STSTEM WIRING - FIG. 79 – CONDENSER FAN CONTROL LAYOUT FOR 3 COMPRESSOR..........71 DXST COMPRESSORS UNITS...... 189 FIG. 34 – ELEMENTARY WIRING DIAGRAM - 4 FIG. 80 – CONDENSER FAN CONTROL LAYOUT FOR COMPRESSOR..........72 DXST COMPRESSORS UNITS...... 191 YORK INTERNATIONAL...
The unit warranty will be void if any modifi cation to the unit is carried out without prior written approval from YORK YCAS chillers are manufactured to the high est York International. design and construction standards to en sure high per-...
This manual and any other document supplied with the unit, are the property of YORK which reserves all rights. They may not be reproduced, in whole or in part, with out prior written authorization from an authorized YORK representative.
(Sys tem 4) can also be used to stop the re spec tive sys tem in an emer gen cy. When op er at ed, CB4 re moves the elec tri cal supply from the con trol sys tem, thus shut ting down the unit. YORK INTERNATIONAL...
INTRODUCTION All exposed power wiring is be routed through liquid- tight, non-metallic conduit. YORK YCAS chillers are designed for water or wa- ter-glycol cooling. All units are designed to be lo cat ed General Description outside on the roof of a building or at ground level.
Condenser The fi n and tube condenser coils are manufactured from seamless, internally enhanced, high condensing co ef fi cient, corrosion resistant copper tubes arranged in 00485VIP FIG. 2 – SCREW COMPRESSOR YORK INTERNATIONAL...
Economizer (Models YCAS 773, 953, 1093 and 1263) The oil (YORK “L” oil – a POE oil used for all A plate and frame heat exchanger (economizer) is fi tted re frig er ant applications), which fl ows back into the to both refrigerant circuits on models YCAS 773, 953, com pres sor through a replaceable 0.5 - 3.0 micron...
ON/OFF switch, microcomputer keypad and display, system that has fault ed on high motor current. mi cro pro ces sor board, I/O expansion board, relay boards and power supply board. YORK INTERNATIONAL...
It is recommended that a YORK imbalance > 17%. Unloaded phase to phase cur rent Ser vice Tech ni cian or the YORK imbalance > 25%. fac to ry be con sult ed before chang ing Improper in com ing phase ro ta tion.
“Op er at ing Current” to the measured half line current. The “Op er at ing Current” is given by 0.65 X factory Additional information on the 2ACE MP module may overload cur rent setting. be found on page 138. YORK INTERNATIONAL...
• Up to 6 fault shut down conditions. (4 in YCAS 3 closed 1S (SYS 1) or 2S (SYS 2) con tacts, en er giz ing, Compressor and YCAS 4 Compressor). 1TRX (SYS 1) or 2TRX (SYS 2). 1TRX or 2TRX YORK INTERNATIONAL...
RS-232 port via a separate print er. or dry contact closure input from the BAS. Program A YORK ISN Building Automation System can pro- For setting low leaving liquid temperature cutout, 300 vide a Pulse Width Modulated (PWM) signal direct to...
(Factory- or fi eld-mounted). Louvered panels (full unit) enclosure – Louvered panels over condenser coils and around the bottom of the unit (Factory- or fi eld-mounted). YORK INTERNATIONAL...
Units with remote evaporators will have the chiller and Major damage must be reported immediately to your remote evaporator charged with nitrogen. lo cal YORK representative. MOVING THE CHILLER If the unit is to be put into storage, prior to installation,...
4-3/4" (120 mm) wide at the con tact tion the same requirement of static pres sure loss ap plies points. This will allow vibration isolators to be fi tted as for ducts and at ten u a tors stated above. if required. YORK INTERNATIONAL...
DO NOT remove the four 3/8" bolts, 3, mounting the in the Tech ni cal Data Section of this corner brackets, 2, to the frame rails. manual, (page 102). COMPRESSOR BASE SUPPORT RAIL CHANNEL BASE LD09131 FIG. 5 – COMPRESSOR MOUNTING YORK INTERNATIONAL...
PSIG) working pres sure and hav ing a 1" N.P.T. con- nection can be obtained from YORK as an ac ces so ry PIPEWORK CONNECTION for the unit. Al ter na tive ly a dif fer en tial pres sure switch sited across an orifi...
fl ow to other units. Aerated, brackish or salt water is not recommended for use in the water system(s). YORK recommends that Thermometer and pressure gauge connections should a wa ter treatment specialist is consulted to determine...
No more than 3 feet (1 meter) of light the evaporator to the compressors. con struc tion ductwork should be supported by the unit. Where cross winds may occur, any ductwork must be sup port ed to prevent side loading on the unit. YORK INTERNATIONAL...
Flow Switch If required, a remote emergency stop de vice can be wired A chilled water fl ow switch, (either by YORK or others) into the unit. The device should be wired into ter mi nals MUST be installed in the leaving water piping of the 31 and 32 (Figs.
It is important to check that the correct pri ma ry Compressor Oil tapping has been used: To add oil to a circuit - connect a YORK hand oil pump (Part No. 470-10654-000) to the 1/4" oil charging valve With the supply voltage to the unit turned off, remove on the oil separator piping with a length of clean hose the lid to the transformer box.
(off set) is to be used, the maximum reset must be pro- wired into the control panel correctly using shielded grammed by pressing the ‘Remote Reset Temp’ key. (See Section 6.) YORK INTERNATIONAL...
After several min utes operation and providing a full charge of re frig er ant is in the system, the bubbles will disappear and be re placed by a solid column of liquid. YORK INTERNATIONAL...
Page 43
FORM 201.19-NM8 (804) This page intentionally left blank. YORK INTERNATIONAL...
The units are designed to work independently, or in Once the unit has been started, all operations are fully con junc tion with other equipment via a YORK ISN automatic. After an initial period at minimum capacity build ing management system or other automated con- on the lead compressor, the control system will adjust trol sys tem.
Page 45
FORM 201.19-NM8 (804) This page intentionally left blank. YORK INTERNATIONAL...
LD03504 • Actual Measured ∆P = 12' H • Corrected ∆P = 12'/1.3 = 9.2' H FIG. 16 – GLYCOL CORRECTION FACTORS • From Flow Rate and Pressure Drop Chart, locate ß ow @ 9.2' ≈ 300 GPM YORK INTERNATIONAL...
Page 47
1215 NOTES: 1. For leaving brine temperature below 5 °C, contact your nearest YORK ofÞ ce for application requirements. 2. For leaving water temperature higher than 13°C, contact the nearest YORK ofÞ ce for application guidelines. 3. The evaporator is protected against freeze-up to -28.8°C with an electrical heater as standard.
LOW NOISE FAN STD FAN 8-POLE MOTOR 8-POLE MOTOR 8-POLE MOTOR MODEL 6-POLE W/COMPRESSOR 8-POLE W/COMPRESSOR W/ PERIMETER KIT MOTOR BLANKET & PERIMETER KIT MOTOR BLANKET (DISCHARGE LINE WRAPPED) (DISCHARGE LINE WRAPPED) 0685EB 0775EB 0835EB 0905EB 0965EB 1065EB 1135SB 1215EB YORK INTERNATIONAL...
COMPRESSOR MODEL AND VOLTAGE CODE DXS45LA – MOTOR CODE A DXS36LA – MOTOR CODE A DXS24LA – MOTOR CODE (TBD) (B5N, B5E, B6N, B6E) (A5N, A5E, A6N, A6E) (C5N, C5E, C6N, C6E) VOLTAGE CODE- MAX KW MAX AMPS YORK INTERNATIONAL...
Terminal Block for Customer Low Voltage (Class 2) Connections. See Note 2 2. Contacts must be suitable for switching 24VDC, (Gold Terminal Block for YORK Connections Only contacts recommend). Wiring shall not be run in the same conduit with any line voltage wiring.
Technical Data FORM 201.19-NM8 (804) ELEMENTARY WIRING DIAGRAM YCAS0685 - YCAS0965 (3 COMPRESSOR) FIG. 24 – ELEMENTARY WIRING DIAGRAM DXST DIRECT DRIVE CONTROL CIRCUIT LD010031 YORK INTERNATIONAL...
Page 61
Ad- pressed with a YORK P/N 031-00808-000 sup pres sor across the ditionally, con trol wir ing not con nect ed to the Smart Panel should not re lay/con tac tor coil.
Technical Data FORM 201.19-NM8 (804) CONNECTION WIRING DIAGRAM 035-15937-104 Rev E Power Panel LD010035 FIG. 27 – CONNECTION DIAGRAM 3 COMPRESSOR POWER PANEL YORK INTERNATIONAL...
Page 65
FORM 201.19-NM8 (804) Electronic Panel 035-15937-104 Rev E LD010036 LD09359 YORK INTERNATIONAL...
FORM 201.19-NM8 (804) ELEMENTARY WIRING DIAGRAM YCAS1065 - YCAS1215 (4 COMPRESSOR) 035 16253 103 Rev A 035-16253-10 Rev - A LD09370 FIG. 37 – CONTROL POWER TRANSFORMER KIT YORK INTERNATIONAL...
Terminal Block for Customer Low Voltage (Class 2) Connections. See Note 2 2. Contacts must be suitable for switching 24VDC, (Gold Terminal Block for YORK Connections Only contacts recommend). Wiring shall not be run in the same conduit with any line voltage wiring.
Page 77
FORM 201.19-NM8 (804) This page intentionally left blank. YORK INTERNATIONAL...
Ad- pressed with a YORK P/N 031-00808-000 sup pres sor across the ditionally, con trol wir ing not con nect ed to the Smart Panel should not re lay/con tac tor coil.
FORM 201.19-NM8 (804) ELEMENTARY DIAGRAM DXST STARTER CONTROL CIRCUIT 035-16253-102 Rev D 035-16253 Rev - B 2ACE Motor Protector LD09373 FIG. 47 – CONNECTION DIAGRAM SYSTEM WIRING YORK INTERNATIONAL...
FORM 201.19-NM8 (804) ELEMENTARY DIAGRAM DXST FAN CONTROL CIRCUIT 035-16253-102 Rev D 035-16253-102 Rev - B LD09374 FIG. 48 – CONNECTION DIAGRAM SYSTEM WIRING YORK INTERNATIONAL...
FORM 201.19-NM8 (804) CONNECTION DIAGRAM SYSTEM WIRING STANDARD AND REMOTE EVAP UNITS 035-19206-106 Rev - 035-19206-106 Rev a LD09383 FIG. 49 – CONNECTION DIAGRAM SYSTEM WIRING YORK INTERNATIONAL...
Page 91
FORM 201.19-NM8 (804) CONNECTION DIAGRAM SYSTEM WIRING STANDARD AND REMOTE EVAP UNITS 035-19206-106 Rev a 035-19206-106 Rev - LD09385 FIG. 49 – CONNECTION DIAGRAM SYSTEM WIRING (CONT'D) YORK INTERNATIONAL...
Page 92
FORM 201.19-NM8 (804) COMPRESSOR TERMINAL BOX SYSTEM 1 THROUGH 4 035-19206-106 Rev a LD10054 YORK INTERNATIONAL...
Page 93
FORM 201.19-NM8 (804) This page intentionally left blank. YORK INTERNATIONAL...
Site re stric tions may compromise min i mum clearances indicated below, resulting in un pre dict able air ß ow pat terns and possible di min ished performance. YORK’s unit controls will optimize operation without nui sance high pres sure safety cutout;...
Page 95
FORM 201.19-NM8 (804) DIMENSIONS – YCAS0685 (SI) LD03977 CENTER OF GRAVITY (Alum.) CENTER OF GRAVITY (Cop per) YCAS YCAS 3689 3711 1008 0685 0685 LD03978 YORK INTERNATIONAL...
Site re stric tions may compromise min i mum clearances indicated below, resulting in un pre dict able air ß ow pat terns and possible di min ished performance. YORK’s unit controls will optimize operation without nui sance high pres sure safety cutout;...
Page 97
1034 0905 0905 2438 1981 SYS. #3 SYS. #1 & #2 10" POWER OPENING 10" (4) 57 DIA. RIGGING WATER INLET (BOTH SIDES) WATER OUTLET HOLES (EACH SIDE) 3708 2642 1614 1727 2277 1713 8694 SIDE VIEW LD03970 YORK INTERNATIONAL...
Site re stric tions may compromise min i mum clearances indicated below, resulting in un pre dict able air ß ow pat terns and possible di min ished performance. YORK’s unit controls will optimize operation without nui sance high pres sure safety cutout;...
Page 99
CENTER OF GRAVITY (Copper) YCAS YCAS 4854 1042 4938 1049 1056 0965 0965 2438 1981 SYS. 1&2 (4) 57 DIA. RIGGING 10" 10" HOLES (EACH SIDE) POWER OPENING WATER INLET WATER OUTLET 3992 3607 1727 2277 1713 1614 8694 LD05588 YORK INTERNATIONAL...
Site re stric tions may compromise min i mum clearances indicated below, resulting in un pre dict able air ß ow pat terns and possible di min ished performance. YORK’s unit controls will optimize operation without nui sance high pres sure safety cutout;...
(1.3 m) (2 m) LD09409 NOTES: 1. No obstructions allowed above the unit. 2. Only one adjacent wall may be higher than the unit. 3. Adjacent units should be 10 feet (3 meters) apart. FIG. 54 – CLEARANCES YORK INTERNATIONAL...
1/4" shim be tween the upper load plate and vertical up rights. Lower the equip ment on the blocking or shimmed isolators. Complete piping and fi ll equipment with wa ter, re frig er ant, etc. YORK INTERNATIONAL...
The high pressure oil-free vapor is fed to the ing to the evaporator. air cooled condenser coil where the heat is re moved. On economized models, the fully con densed liquid enters the econ o miz er. YORK INTERNATIONAL...
DIFFERENTIAL PRESSURE CUTOUT CONDENSER COIL COOLER DISCHARGE PRESSURE FAN CONTROL DISPLAY VALUE OIL COOLER COIL HIGH PRESSURE LOAD LIMITING OIL SEPARATOR HIGH TEMPERATURE CUTOUT LOW PRESSURE CUTOUT LOW TEMPERATURE CUTOUT LD09429 FIG. 64 – PROCESS AND INSTRUMENTATION DIAGRAM YORK INTERNATIONAL...
OIL FILTER LOCKING BOLT COVER PLATE OIL FILTER BLEED & EVACUATION POINT LIFTING LUG THREADED HOLE HEATER ECONOMIZER GAS IN DISCHARGE CASE DISCHARGE GAS OUT EVACUATION PORT OIL INLET FROM CONDENSER LD03668 COOLING COIL FIG. 66 – COMPRESSOR COMPONENTS YORK INTERNATIONAL...
Technical Data FORM 201.19-NM8 (804) SYSTEM STARTUP CHECKLIST If it is necessary to add oil, con nect a YORK oil pump to the charging valve on the oil sep a ra tor, JOB NAME: _____________________________ but do not tight en the fl are nut on the delivery SALES ORDER #: ________________________ tub ing.
Damage to the chiller could Sys #1 100% FLA = _________________________Amps result if switch es are im prop er ly Sys #2 100% FLA = _________________________Amps pro grammed. Sys #3 100% FLA = _________________________Amps Sys #4 100% FLA = _________________________Amps YORK INTERNATIONAL...
This Liq Line Temp = ºF (ºC) is due to the com pres sor com ing up to speed and Subcooling = ºF (ºC) lubrication chang ing from liq uid re frig er ant to YORK INTERNATIONAL...
(IF APPLICABLE) (15 TON TXV) load and unload to control water temperature, the chill er is ready to be placed into operation. The economizer superheat should be checked to as sure YORK INTERNATIONAL...
This switch shuts down the entire chiller when placed in the OFF position. The switch must be ON for the chiller to operate. The systems will not pump down at shutdown when the UNIT switch is switched OFF. YORK INTERNATIONAL...
The YORK Screw Chiller Control Panel is a mi cro pro - ces sor based control system fi tted to YCAS liq uid chill- YCAS chillers each have a single split circuit evap o ra tor ers.
(setpoints, clock, cutouts, etc.) I/O Ex pan sion Board which multiplexes them and then are not lost during a power failure or shutdown period feeds them to the Microprocessor Board. re gard less of the time involved. YORK INTERNATIONAL...
Mi cro pro ces sor This could cause evap o ra tor freeze- Board. up in low ambient tem per a tures. Removing 115VAC power to individual circuits also removes power to the compressor heaters, which should also be avoided. YORK INTERNATIONAL...
M1 and M2 contacts, the last 2 faults will show Low CURR/MP/HP, but will have no value for trouble- shooting. The information contained in HISTORY BUFFER #3 will be use- ful on troubleshooting the cause of the Mo tor Pro tec tor fault. YORK INTERNATIONAL...
SWITCH PUSHED TO THE LEFT SIDE VIEW INDICATES ON (SWITCHES PLACED IN THE ON POSITION ADD TO EQUAL THE OVERLOAD SETTING VALUE. FOR EXAMPLE, IF SWITCH 2 AND 128 ARE ON, THE DISPLAY WILL FLASH HA130) FIG. 72 – MOTOR PROTECTION MODULE YORK INTERNATIONAL...
Current Limit may be viewed on the the de vice must be sup pressed with a EMS Current Lim it ing Dis play under sup pres sor YORK Part Number 031- the Mo tor Current Key (see Sec tion 00808-000 across the in duc tive coil.
Page 141
For example, with a programmed setpoint of 44°F (7°C), with a sup pres sor YORK Part Num ber after a 4 second pulse and a programmed maximum off set 031-00808-000 across the in duc tive of 40°F (22°C), the temperature offset would equal:...
NOTE : Dimple is positioned at top edge (3A) Dip Switch Set (8 switches) System Switches S2 = System 1 S3 = System 2 S2 to S5 S4 = System 3 S5 = System 4 FIG. 73 – COMPONENT LAYOUT YORK INTERNATIONAL...
5 minutes. After 5 minutes has elapsed, the heat er will shut off if the discharge temperature rises above 150 °F (66°C) and will turn on when the dis charge tem per a ture is equal to or less than 150 °F (66°C). YORK INTERNATIONAL...
RC lead to the compressor with the shortest anti-recycle sup pres sor YORK Part Num ber 031- time in a an effort to provide cooling quick ly. 00808-000 across the in duc tive coil.
The second timer assures that a minimum of 3 minutes elapses from the time the economizer turns off to the next time it is called to turn on again. YORK INTERNATIONAL...
Page 147
FORM 201.19-NM8 (804) This page intentionally left blank. YORK INTERNATIONAL...
S Y S C O M P R U N N I N G applicable to represent the system number where mes- sag es apply to individual systems. This message indicates that the respective compressor is running due to demand. YORK INTERNATIONAL...
Once a low battery condition is detected, the only way to run the chiller is to use the Manual Override key - see Section 8.7.4. This al lows re pro gram ming of setpoints, cutouts, and sched ule. YORK INTERNATIONAL...
Therefore, "Automatic" is typically ambient or load conditions occur. See Anticipatory Un- selected and programmed under the loading Controls Page 173 for detailed operation. PROGRAM key. See page 182. YORK INTERNATIONAL...
This the chill er must be manually reset. See Section 8.2 feature is programmable and can also be used to shut (page 182). down the chiller at a temperature where continued run- YORK INTERNATIONAL...
Fail ure to repair the cause of the fault while manually al low ing re pet i tive re starts may cause fur ther ex pen sive damage to the system. YORK INTERNATIONAL...
130 - 150°F (54 - 66°C). The High Oil Temperature Safety is activated after 2 minutes of compressor operation, after which if oil tem per a ture is above 225°F (107°C) for more than 3 sec onds, the compressor will shut down. YORK INTERNATIONAL...
Page 154
This may result from loss of re frig er ant, a de- fective contactor, power problems, or from a compressor that is not pumping due to a mechanical malfunction. YORK INTERNATIONAL...
R-407C. This safety uses the Evaporator Inlet Refrigerant Temp Sen sors to mon i tor evaporator inlet refrigerant tem per a ture on each system. These sensors are only installed on R-407C units. YORK INTERNATIONAL...
M C H L T 4 3 . 8 ° the values which are being displayed, but are outside the ability of the micro to give an actual reading. This YORK INTERNATIONAL...
Display Limits: Minimum - 4.6°F (-20.3°C) valve solenoid in the form of a voltage signal. To the Maximum 137.9°F (58.8°C) mi cro pro ces sor, STEP 0 = fully unloaded and STEP 75 = fully loaded. YORK INTERNATIONAL...
The Options key provides a display of op tions which are Cutout setting at 25°F (-4°C) and is not ad just able. programmed by the po si tions of the S1 Dip Switch es on the Mi cro pro ces sor Board. Proper pro gram ming of YORK INTERNATIONAL...
Place the switch in the CLOSED position selects the type of chiller as an air cooled chiller (YCAS). The DO NOT USE THIS POSITION. switch MUST always be in the CLOSED position. Nuisance trips at start-up could result. Incorrect programming may cause damage to the chiller. YORK INTERNATIONAL...
The following keys can be scrolled using the Function E L E C T R O N I C Key: Chilled Liquid Temps, System # Data, Motor Cur- rent and Options. Placing the switch in the CLOSED position, confi gures YORK INTERNATIONAL...
“rate control” and “temperature deviation from setpoint” to de ter mine Information available using the Operating Data key is de- when loading/unloading should occur. YORK INTERNATIONAL...
Page 162
– YorkTalk via ISN or Remote Control Center (remote mode). PWM CURR – EMS PWM Current Limiting Enabled PWM TEMP – EMS PWM Temp. Reset Enabled CUR/TEMP – EMS PWM Current Limiting & Temperature Reset Enabled YORK INTERNATIONAL...
This message displays the accumulated Run Time since printouts for the appropriate number of systems: the last start in Days (D), Hours (H), Minutes (M), and Seconds (S). YORK INTERNATIONAL CORPORATION MILLENNIUM SCREW CHILLER S Y S L L S V...
No. 1. After the ENTER Key is pressed, a mes sage in- dicating the time and date of the Fault Shut down will appear: S H U T D O W N O C C U R R E D 5 : 5 9 A M N O V YORK INTERNATIONAL...
Page 165
1 0 0 % F L A This message indicates whether heat recovery is dis- abled or enabled. (HEAT RECOVERY MUST BE This message shows the programmed %FLA Motor DISABLED) Current Unload at the time of the fault. YORK INTERNATIONAL...
Page 166
N U M B E R This message indicates the compressor motor current in amps and as a percentage of Full Load Amps. This message indicates which system was in the lead at the time of the fault. YORK INTERNATIONAL...
Page 167
R E F R I G T E M P 2 8 . 2 ° F This message, which is only displayed if the unit is in R-407C mode, indicates the refrigerant temperature at the inlet of the evaporator. YORK INTERNATIONAL...
ECONOMIZER TXV SOLENOID An example of the HISTORY Printout is shown be- CONDENSER FAN STAGE low: COMPRESSOR HEATER WYE-DELTA RELAY YORK INTERNATIONAL CORPORATION SYSTEM 2 DATA MILLENNIUM SCREW CHILLER COMPRESSORS STATUS SAFETY SHUTDOWN NUMBER 1 RUN TIME 0- 0-15-26 D-H-M-S...
“AM” or “PM” on the display. For ex- original values will be returned. am ple, pressing the " key when the cursor is on “PM” changes it to “AM.” YORK INTERNATIONAL...
“Control Range” and is best the slide valve solenoid of each compressor. Voltage de scribed as the maximum acceptable + and - deviation increases with load (0 - approximately 9VDC at full from Setpoint. load). YORK INTERNATIONAL...
Page 171
2nd and 3rd lag compressor will of the mechanism, a position less than 75, possibly 60, be alternately loaded until the leaving chilled liquid could also mean that the compressor is fully loaded. A temperature is satisfi ed. YORK INTERNATIONAL...
Page 172
Chill er fault on a Low Wa ter Tem- > 80 % per a ture cut-out under the fol low ing > 90 % conditions: a) if chilled liq uid tem- > 95 % per a ture falls below the low end of the YORK INTERNATIONAL...
Page 173
S Y S D S C H / O I L I N H I B > 108 % S Y S D S C H / O I L I N H I B > 115 % YORK INTERNATIONAL...
“0” for val ues After the Setpoint and Range is keyed in, press the less than 10°F (or 5.6°C). Press the ENTER Key to store ENTER Key to store the data in memory. the new value in memory. YORK INTERNATIONAL...
Press ENTER to move on to the hour part of the display. Next, key in the time (hours/minutes) using a leading Press ing the Set Time key a second time enters “display” mode in which the cursor will dis ap pear and the “live” clock will be dis played. YORK INTERNATIONAL...
ON position, all 00.00s should be programmed into the oc ca sion al ly. daily schedule. This can be done manually for in di vid u al days or for all days by pressing Cancel and En ter for the Monday Start/Stop schedule. YORK INTERNATIONAL...
Enter key is exceeded for 3 seconds, the system will shut down. is pressed and the display will scroll on to the next pro- Normally, air-cooled chillers, such as YCAS chillers, gram ma ble value. YORK INTERNATIONAL...
Page 179
fi rst.), suction pressure is monitored as long 18°F (10°C) below the lowest temperature of the pro- as the compressor runs. For the fi rst 270 sec onds of run- grammed chilled liquid Control Range (Section 6). YORK INTERNATIONAL...
Page 180
Enter key to store the value into lim it ing”. This is important when demand limiting is memory and scroll to the next display. crit i cal due to power requirements or limitations in the build ing (See also Section 1.10). YORK INTERNATIONAL...
Page 181
S E T P O I N T = 1 2 . 0 º F The EEV superheat setpoint is programmable. The setpoint can be programmed for 9.0ºF (5.0ºC) to 15ºF (8.3ºC) with 12.0ºF (6.6ºC) as the default. YORK INTERNATIONAL...
This will preset all programmable values un der the Program key to values that will allow operation of the chiller under most operating conditions. This al lows quick start-up pro gram ming for typical chilled wa ter ap pli ca tions. YORK INTERNATIONAL...
The purpose of the EEV is to meter a fl ow of liquid refrigerant into the evaporator to maintain a superheat 120 VAC PILOT SOLENOID EXPANSION VALVE 24 VAC HEAT MOTOR LD09132 FIG. 78 – ELECTRONIC EXPANSION VALVE YORK INTERNATIONAL...
fi rst. is the PWM per cent age that will be sent to the ETRE heat motor. This PWM output is the percentage of a 1 second pe ri od that the 24VAC heat motor power signal is energized. YORK INTERNATIONAL...
Page 186
S E N S O R F A I L U R E LIQUID LINE SOLENOID ECONOMIZER TXV SOLENOID OFF(YCAS) OIL COOLING SOLENOID OFF(YCWS) HEAT RECOVERY SOLENOID OFF(B HR) DISCHARGE COOLING SOLENOID OFF(EC,LT) CONDENSER FAN STAGE COMPRESSOR HEATER WYE-DELTA RELAY YORK INTERNATIONAL...
The Expansion Valve type selection is viewable un der the OP TIONS key. TABLE 4 – PROGRAMMABLE VALUES TABLE (MINIMUM/MAXIMUM) PROGRAM VALUE MODE LOW LIMIT HIGH LIMIT DEFAULT 15.0 12.0 º º º SUPERHEAT SETPOINT (5.0 º º º YORK INTERNATIONAL...
EEV output. · If everything checks out, it is possible that the EEV has failed. If the small charge in the bulb leaks, the valve will not be able to open and the entire EEV must be replaced. YORK INTERNATIONAL...
<215 PSIG & <85°F 15M, 16M, 17M, 18M, 19M 230, 231, 232 10, 14, 15 SYSTEM 3 IS ALWAYS EQUIPPED WITH 4 FANS. * At ambients above 85ºF, stages 3, 4, 5, and 6 will all turn on at 240 psig. YORK INTERNATIONAL...
180 ºF default Oil Cooling Diff 9 to 18 ºF **** 9 ºF default Discharge Cooling On 176.0 to 239.0 ºF 212.0 ºF default Discharge Cooling Diff 7.2 to 27.0 ºF 18 ºF default Data Logging Mode OFF or ON YORK INTERNATIONAL...
Hot Flow Switch (Heat Recovery only) ANALOG OUTPUTS Table 16 lists all the analog outputs and what output board they are on. TABLE 16 - ANALOG OUTPUTS I/O Expansion J2-1 Sys 1 Slide Valve I/O Expansion J12-1 Sys 2 Slide Valve YORK INTERNATIONAL...
TEST POINTS: Suction Pressure: System 1: ............Microboard J13-7/1 System 2: ............Microboard J14-7/1 Oil Pressure: System 1: ............Microboard J13-8/3 System 2: ............Microboard J14-8/3 Discharge Pressure: System 1: ............Microboard J15-8/3 System 2: ............Microboard J15-7/1 YORK INTERNATIONAL...
44-47 Sys 1 Discharge Pressure 48-51 Sys 1 % Full Load Amps 52-55 Sys 1 Total Run Hours 56-59 Sys 1 Total Number of Stats 60-63 Sys 1 Anti-Recycle Timer 64-67 Anti-Coincident Timer 68-71 Sys 2 Oil Temperature YORK INTERNATIONAL...
Page 202
*Sys 1 Fault Code *Sys 2 Operatioanal Code *Sys 2 Fault Code Sys 1 Slide Valve Step Sys 1 Condenser Fan Stages Running (0-6) Sys 2 Slide Valve Step Sys 2 Condenser Fan Stages Running (0-6) Lead Compressor Number Debug Code YORK INTERNATIONAL...
Page 203
Cooling Range 174-177 Sys 1 Discharge Superheat 178-181 Sys 2 Suction Temperature 182-185 Sys 2 Discharge Temperature 186-189 Sys 2 Suction Superheat 190-193 Sys 2 Discharge Superheat Digital S1-7 Expansion Valve Type: 0=TXV, 1=EEV S1-8 SPARE — — — YORK INTERNATIONAL...
* The operational and fault codes are defi ned in Table 19. Note that this table of fault and operational codes is for all DX products. The codes that are grayed out are not used on this unit. YORK INTERNATIONAL...
Page 205
FORM 201.19-NM8 (804) This page intentionally left blank. YORK INTERNATIONAL...
YORK Service Agent. for these regular maintenance requirements and/or en ter into a maintenance agreement with a York In ter na tion al Unit Status: Press the ‘STATUS’ key on the keypad ser vice organization to protect the operation of the unit.
Nor mal ly a ‘minor’ service should be carried out every three to six months and a ‘major’ service once a year. It is recommended that your local YORK Service Cen ter is contacted for recommendations for in di vid u al sites. ON-BOARD BATTERY BACK-UP U17 is the Real Time Clock chip that maintains the date/ time and stores customer programmed setpoints.
Page 208
YORK Order No. ________________________ CHILLER/COMPRESSOR Compr. Ser. No. _________________________ Operating Log Unit Ser. No. ___________________________ Refrigerant_____________________________ Date Time Hour Meter Reading Equipment Room Temp./Outdoor Temp. Suction Pressure Suction Temperature Suction Superheat Discharge Pressure Actual Discharge Temperature Oil Pressure Oil Temperature...
Page 209
* Reserved for customer use for any special site determined requirements. This procedure must be performed at the speciÞ ed time interval by an Industry CertiÞ ed Technician who has been trained and qualiÞ ed to work on this type of YORK equipment.
Other spare parts vary depending on the unit mod el. Review the chiller Renewal Parts Manual or Contact your local YORK Sales and Ser vice Center for in for ma tion (Please quote the unit model num ber and serial number).
Check that the compressor unloads correctly. Measured temperature is incorrect. Check water temp sensor and wiring. Chiller FAULT: VAC Check main supply is stable and within allowable UNDERVOLTAGE Poor main supply voltage. limits. displayed. Check for voltage dip on compressor start. YORK INTERNATIONAL...
Page 213
Check operation of economizer, TXV, and liquid solenoid valve. SYS # CURR LIMITING High compressor motor current Check if liquid temperature is within operating limits. displayed has activated unloading. Check if ambient air temperature is above operating (Compressor current un- limits. loading.) YORK INTERNATIONAL...
Except for reciprocating compressors, which YORK war- rants for a period of one year from date of ship ment, YORK in law or in fact, including the war ran ties of warrants reconditioned or re place ment ma te ri als, or start- merchantability and fi...