Water cooled liquid chiller 91 tons through 216 tons 320 kw through 760 kw 60hz style a
Table of Contents

Advertisement

Incoming Wire Range Selections
CHILLER
VOLT
TERM
MODEL
C O D E
BLK
YCWS0100SC
#2 - 4/0 AWG
YCWS0120SC
#2 - 4/0 AWG
YCWS0140SC
#2/0 - 500 KCM
YCWS0180SC -17 #2/0 - 500 KCM
YCWS0200SC
#2/0 - 500 KCM
YCWS0220SC
#2/0 - 500 KCM
YCWS0240SC
(2) #2 - 4/0 AWG (2) # 6 - 1/0 AWG
YCWS0100SC
#2 - 4/0 AWG
YCWS0120SC
#2 - 4/0 AWG
YCWS0140SC
#2 - 300 KCM
YCWS0180SC -28 #2 - 300 KCM
YCWS0200SC
#2/0 - 500 KCM
YCWS0220SC
#2/0 - 500 KCM
YCWS0240SC
#2/0 - 500 KCM
YCWS0100SC
#6 - 1/0 AWG
YCWS0120SC
#6 - 1/0 AWG
YCWS0140SC
#2 - 4/0 AWG
YCWS0180SC -40
#2 - 4/0 AWG
YCWS0200SC
#2 - 4/0 AWG
YCWS0220SC
#2 - 4/0 AWG
YCWS0240SC
#2 - 4/0 AWG
YCWS0100SC
#6 - 1/0 AWG
YCWS0120SC
#6 - 1/0 AWG
YCWS0140SC
#6 - 1/0 AWG
YCWS0180SC -46
#6 - 1/0 AWG
YCWS0200SC
#2 - 4/0 AWG
YCWS0220SC
#2 - 4/0 AWG
YCWS0240SC
#2 - 4/0 AWG
YCWS0100SC
#18 - 2 AWG
YCWS0120SC
#18 - 2 AWG
YCWS0140SC
#6 - 1/0 AWG
YCWS0180SC -58
#6 - 1/0 AWG
YCWS0200SC
#6 - 1/0 AWG
YCWS0220SC
#6 - 1/0 AWG
YCWS0240SC
#2 - 4/0 AWG
NOTES:
(for Electrical Data on pages 26-28)
1. Minimum Circuit Ampacity (MCA) is based on 125% of the rated load amps for the largest motor plus 100% of
the rated load amps for all other loads included in the circuit, per N.E.C. Article 430-24. If the optional Factory
Mounted Control Transformer is provided, add the following MCA values to the electrical tables for the system
providing power to the transformer: -50, add 5 amps;
2. The minimum recommended disconnect switch is based on 115% of the rated load amps for all loads included
in the circuit, per N.E.C. Article 440.
3. Minimum fuse size is based upon 150% of the rated load amps for the largest motor plus 100% of the rated
load amps for all other loads included in the circuit to avoid nuisance trips at start-up due to lock rotor amps. It
is not recommended in applications where brown outs, frequent starting and stopping of the unit, and/or opera-
tion at ambient temperatures in excess of 35ºC (95ºF) is anticipated.
4. Maximum fuse size is based upon 225% of the rated load amps for the largest motor plus 100% of the rated
load amps for all other loads included in the circuit, per N.E.C. Article 440-22.
40
MULTIPOINT WIRING SYSTEM #1
TERMINAL BLK
N-F DIS
CUSTOMER
SW
GROUND
# 8 - 2 AWG
#4 - 300 KCM
# 8 - 2 AWG
#4 - 300 KCM
# 4 - 3/0 AWG
#6 - 350 KCM
# 4 - 3/0 AWG
#4 - 300 KCM
# 4 - 3/0 AWG
# 8 - 350 KCM
# 4 - 3/0 AWG
250 - 500 KCM
(2) #3/0 - 250 KCM
# 8 - 2 AWG
#4 - 300 KCM
# 8 - 2 AWG
#4 - 300 KCM
# 6 - 1/0 AWG
#4 - 300 KCM
# 6 - 1/0 AWG
#4 - 300 KCM
# 4 - 3/0 AWG
#6 - 350 KCM
# 4 - 3/0 AWG
250 - 500 KCM
# 4 - 3/0 AWG
250 - 500 KCM
# 8 - 2 AWG
#14 - 1/0 AWG
# 8 - 2 AWG
#14 - 1/0 AWG
# 8 - 2 AWG
#4 - 300 KCM
# 8 - 2 AWG
#4 - 300 KCM
# 8 - 2 AWG
#4 - 300 KCM
# 8 - 2 AWG
#4 - 300 KCM
# 8 - 2 AWG
#4 - 300 KCM
# 8 - 2 AWG
#14 - 1/0 AWG
# 8 - 2 AWG
#14 - 1/0 AWG
# 8 - 2 AWG
#4 - 300 KCM
# 8 - 2 AWG
#14 - 1/0 AWG
# 8 - 2 AWG
#4 - 300 KCM
# 8 - 2 AWG
#4 - 300 KCM
# 8 - 2 AWG
#4 - 300 KCM
# 8 - 2 AWG
#14 - 1/0 AWG
# 8 - 2 AWG
#14 - 1/0 AWG
# 8 - 2 AWG
#14 - 1/0 AWG
# 8 - 2 AWG
#14 - 1/0 AWG
# 8 - 2 AWG
#14 - 1/0 AWG
# 8 - 2 AWG
#14 - 1/0 AWG
# 8 - 2 AWG
#4 - 300 KCM
(Cont.)
N-F DIS SW
CUSTOMER
CKT.BRKR
GROUND
# 6 - 1/0 AWG
#6 - 350 KCM
# 6 - 1/0 AWG
#4 - 300 KCM
# 6 - 1/0 AWG
250 - 500 KCM
# 6 - 1/0 AWG
250 - 500 KCM
# 4 - 3/0 AWG
250 - 500 KCM
# 4 - 3/0 AWG
250 - 500 KCM
# 4 - 3/0 AWG
(3) 2/0 - 400 KCM
# 6 - 1/0 AWG
#4 - 300 KCM
# 8 - 2 AWG
#4 - 300 KCM
# 6 - 1/0 AWG
#4 - 300 KCM
# 6 - 1/0 AWG
250 - 500 KCM
# 6 - 1/0 AWG
250 - 500 KCM
# 4 - 3/0 AWG
250 - 500 KCM
# 4 - 3/0 AWG
250 - 500 KCM
# 8 - 2 AWG
#4 - 300 KCM
# 8 - 2 AWG
#4 - 300 KCM
# 8 - 2 AWG
#4 - 300 KCM
# 8 - 2 AWG
#4 - 300 KCM
# 8 - 2 AWG
#4 - 300 KCM
# 8 - 2 AWG
#4 - 300 KCM
# 6 - 1/0 AWG
#6 - 350 KCM
# 8 - 2 AWG
#14 - 1/0 AWG
# 8 - 2 AWG
#14 - 1/0 AWG
# 8 - 2 AWG
#4 - 300 KCM
# 8 - 2 AWG
#4 - 300 KCM
# 8 - 2 AWG
#4 - 300 KCM
# 8 - 2 AWG
#4 - 300 KCM
# 8 - 2 AWG
#4 - 300 KCM
# 8 - 2 AWG
#14 - 1/0 AWG
# 8 - 2 AWG
#14 - 1/0 AWG
# 8 - 2 AWG
#2 - 4/0 AWG
# 8 - 2 AWG
#2 - 4/0 AWG
# 8 - 2 AWG
#4 - 300 KCM
# 8 - 2 AWG
#4 - 300 KCM
# 8 - 2 AWG
#4 - 300 KCM
YORK INTERNATIONAL
CKT.BRKER
CUSTOMER
GROUND
# 6 - 1/0 AWG
# 6 - 1/0 AWG
# 4 - 3/0 AWG
# 4 - 3/0 AWG
# 4 - 3/0 AWG
# 4 - 3/0 AWG
(2) # 2 - 4/0 AWG
# 6 - 1/0 AWG
# 6 - 1/0 AWG
# 4 - 3/0 AWG
# 4 - 3/0 AWG
# 4 - 3/0 AWG
# 4 - 3/0 AWG
# 4 - 3/0 AWG
# 8 - 2 AWG
# 8 - 2 AWG
# 6 - 1/0 AWG
# 6 - 1/0 AWG
# 6 - 1/0 AWG
# 6 - 1/0 AWG
# 6 - 1/0 AWG
# 8 - 2 AWG
# 8 - 2 AWG
# 8 - 2 AWG
# 8 - 2 AWG
# 6 - 1/0 AWG
# 6 - 1/0 AWG
# 6 - 1/0 AWG
# 8 - 2 AWG
# 8 - 2 AWG
# 8 - 2 AWG
# 8 - 2 AWG
# 8 - 2 AWG
# 8 - 2 AWG
# 8 - 2 AWG