LCWT
30.0
KWo
KWi
(°C)
YCWS0200SC
5.0 632.7
111.7
6.0 657.1
111.8
7.0 681.1
111.8
8.0 705.4
111.7
9.0 730.4
111.5
10.0 756.0
111.3
YCWS0220SC
5.0 690.4
123.1
6.0 714.3
123.2
7.0 741.9
123.2
8.0 768.6
123.2
9.0 795.9
123.1
10.0 823.9
122.8
YCWS0240SC
5.0 745.5
134.7
6.0 772.8
134.9
7.0 800.9
134.9
8.0 829.6
134.9
9.0 859.0
134.8
10.0 897.9
134.5 1032.0
NOTES:
1. KWo = Unit kW Cooling Capacity Output
2. KWi= Compressor kW Input
3. COP = Coefficient of Performance
4. LCWT= Leaving Chilled Water Temperature
5. Ratings based on 0.047 l/s cooler water per kW.
YORK INTERNATIONAL
LEAVING CONDENSER WATER TEMPERATURE (°C)
KW
COP
KWo
744.0
5.7
599.6
768.0
5.9
623.4
792.0
6.1
646.6
817.0
6.3
668.4
842.0
6.6
694.6
867.0
6.8
719.3
813.0
5.6
654.5
837.0
5.8
679.1
865.0
6.0
704.3
891.0
6.2
730.1
919.0
6.5
756.5
946.0
6.7
783.6
880.0
5.5
706.5
907.0
5.7
733.1
935.0
5.9
760.4
964.0
6.2
788.2
993.0
6.4
816.6
6.7
845.7
35.0
KWi
KW
COP
125.6
725.0
4.8
125.9
749.0
5.0
126.1
772.0
5.1
126.3
794.0
5.3
126.4
821.0
5.5
126.5
845.0
5.7
138.3
792.0
4.7
138.6
817.0
4.9
138.9
843.0
5.1
139.2
869.0
5.3
139.4
896.0
5.4
139.5
923.0
5.6
151.2
857.0
4.7
151.6
884.0
4.8
152.0
912.0
5.0
152.3
940.0
5.2
152.5
969.0
5.4
152.7
998.0
5.5
FORM 201.24-EG1
40.0
KWo
KWi
KW
567.2
140.4
707.0
589.0
140.7
729.0
609.7
141.0
750.0
632.8
141.3
774.0
657.8
141.6
799.0
681.8
141.9
823.0
617.7
154.5
772.0
641.4
154.9
796.0
664.2
155.2
819.0
690.2
155.6
845.0
716.4
156.0
872.0
742.5
156.4
898.0
666.6
168.9
835.0
692.3
169.3
861.0
718.6
169.7
888.0
745.6
170.2
915.0
773.2
170.6
943.0
801.3
171.0
972.0
COP
4.0
4.2
4.3
4.5
4.6
4.8
4.0
4.1
4.3
4.4
4.6
4.8
4.0
4.1
4.2
4.4
4.5
4.7
17