Centrifugal liquid chillers styles a & b with microcomputer control center part 371-01200-004 for electro-mechanical starter & solid state starter (57 pages)
Introduction York YCWS Water Cooled Screw Chillers YORK YCWS Water-Cooled models provide chilled water for all air conditioning applications that use central station air handling or terminal units. They are completely self-contained and are designed for indoor (new or retrofit) installation. Each unit includes accessible semi-hermetic screw compressors, a liquid cooler, water cooled condenser, and a user-friendly, diagnostic Microcomputer Control Center all mounted on a rugged steel base.
The unit will be pressure-tested, evacuated, and charged with Refrigerant-22, and York ‘L’ (POE) synthetic oil. There will be an operational test, with water flowing through the cooler, to check that each control device operates correctly.
Page 5
(EPROM) to eliminate chiller failure due to AC power failure. The microprocessor can be directly connected to a YORK ISN Building Automation System via the standard on- board RS485 communications port. This option also pro- vides open system compatibility with other communica- tions networks.
Page 6
Liq- uid temperature setpoint reset signal from YORK ISN or building automation system (by others) via: • Pulse width modulated (PWM) input for up to 40°F (22°C) total reset as standard.
• Printed circuit board to accept 4 to 20 milliamp, 0 to 10 VDC, or dry contact closure input from the BAS. • A YORK ISN Building Automation System can provide a Pulse Width Modulated (PWM) signal direct to the standard control panel via the standard onboard RS485 port.
Page 9
The low pressure liquid refrigerant then returns to the cooler. Each refrigerant circuit utilizes liquid injection, maintaining efficient oil temperature operation within the compressor. YORK INTERNATIONAL Separators Oil Cooling Liquid Injection...
Selection Data GUIDE TO SELECTION Complete water chilling capacity ratings for YORK YCWS chillers are shown on the following pages to cover the majority of job requirements. For any application be- yond the scope of this Engineering Guide, consult your nearest YORK Office.
Page 13
3. Determine the average full load kW and EER at 95.0 Tons 95.0 X (86.7) = 74KW 111.3 YORK INTERNATIONAL EER = 4. Determine the cond. Heat rejection as follows: Heat Rejection (MBH) 5. Determine GPM condensing water as follows: GPM Condenser Water = 6.
Page 15
4. EER = Chiller Energy Efficiency Ratio (Capacity [Tons x 12] 5. LCWT = Leaving Chilled Water Temperature 6. Ratings based on 2.4 GPM cooler water per ton 7. Ratings certified in accordance with ARI Standard 550/590-98 up to 200 tons. YORK INTERNATIONAL 95.0 TONS 19.5 168.8...
Page 17
1. KWo = Unit kW Cooling Capacity Output 2. KWi= Compressor kW Input 3. COP = Coefficient of Performance 4. LCWT= Leaving Chilled Water Temperature 5. Ratings based on 0.047 l/s cooler water per kW. YORK INTERNATIONAL 35.0 599.6 125.6 725.0 623.4...
Page 19
6. Ratings based on 2.4 GPM cooler water per ton 7. Ratings certified in accordance with ARI Standard 550/590-98 up to 200 tons. 8. For ratings other than 30% glycol, refer to the design 03 dxchill program. YORK INTERNATIONAL 95.0 TONS 10.2...
Page 21
3. COP = Coefficient of Performance 4. LCWT= Leaving Chilled Water Temperature 5. Ratings based on 0.047 l/s cooler water per kW. 6. For ratings other than 30% glycol, refer to the design 03 dxchill program. YORK INTERNATIONAL 35.0 311.0 123.8 434.0...
Page 23
6. Ratings based on 2.4 GPM cooler water per ton 7. Ratings certified in accordance with ARI Standard 550/590-98 up to 200 tons. 8. For ratings other than 30% glycol, refer to the design 03 dxchill program. YORK INTERNATIONAL 95.0 TONS 10.2...
Page 25
3. COP = Coefficient of Performance 4. LCWT= Leaving Chilled Water Temperature 5. Ratings based on 0.047 l/s cooler water per kW. 6. For ratings other than 30% glycol, refer to the design 03 dxchill program. YORK INTERNATIONAL 35.0 314.2 123.7 438.0...
YCWS0140SC YCWS0180SC YCWS0200SC YCWS0220SC YCWS0240SC 1" Isolator Selections - VMC Type CP-4- X Model YCWS0100SC YCWS0120SC YCWS0140SC YCWS0180SC YCWS0200SC YCWS0220SC YCWS0240SC YORK INTERNATIONAL Weight Distribution by Model 1997 1997 2082 2104 2104 2131 2210 2210 2195 3314 3314 3314 3336...
Sound Data Sound Pressure Levels (SPL), dB re 20 microPa in MODEL YCWS0100SC YCWS0120SC YCWS0140SC YCWS0180SC YCWS0200SC YCWS0220SC YCWS0240SC Note: All ‘A’ weighted sound pressure data ± 3 dBA YORK INTERNATIONAL (Cont.) DEFL. 19mm 191mm 95mm 13mm 11NC 1” 7.5” 3-3/4”...
Dimensions (English) Mounting Dimensions Model YCWS0100SC 115-5/8 YCWS0120SC 115-5/8 YCWS0140SC 115-5/8 YCWS0180SC 162-7/8 YCWS0200SC 162-7/8 YCWS0220SC 162-7/8 YCWS0240SC 162-7/8 Center of gravity (inches) Model YCWS0100SC YCWS0120SC YCWS0140SC YCWS0180SC YCWS0200SC YCWS0220SC YCWS0240SC 23-3/4 23-3/4 23-3/4 25-3/4 25-3/4 25-3/4 25-3/4 YORK INTERNATIONAL...
Page 33
70-1/2" 20-7/8" 25-15/16" 48" 48" NOTES: 1. CLEARANCES - Recommended YORK clearances to service the unit are as follows: Rear to Wall: Front to Wall: Top: Tube cleaning and removal: 8’ (either end) 2. Shipping skids (not shown) will increase the height of the unit by 6”, but MUST be removed upon in-...
Page 34
2937 YCWS0140SC 2937 YCWS0180SC 4137 YCWS0200SC 4137 YCWS0220SC 4137 YCWS0240SC 4137 Center of gravity (mm) Model YCWS0100SC 1442 YCWS0120SC 1464 YCWS0140SC 1443 YCWS0180SC 2031 YCWS0200SC 2026 YCWS0220SC 2034 YCWS0240SC 2029 All dimensions are in mm unless otherwise noted. YORK INTERNATIONAL...
Page 35
1791 1791 1219 1219 1219 NOTES: 1. CLEARANCES - Recommended YORK clearances to service the unit are as follows: Rear to Wall: Front to Wall: Top: Tube cleaning and removal: 2438mm (either end) 2. Shipping skids (not shown) will increase the height of the unit by 152mm, but MUST be removed upon installation.
YCWS0180SC YCWS0200SC YCWS0220SC YCWS0240SC YCWS0100SC YCWS0120SC YCWS0140SC YCWS0180SC YCWS0200SC YCWS0220SC YCWS0240SC YCWS0100SC YCWS0120SC YCWS0140SC YCWS0180SC YCWS0200SC YCWS0220SC YCWS0240SC (SEE FIG 9 , PAGE 30) SYSTEM #1 MAX DUAL MIN NF CIR. DUAL FUSE DISC SW FUSE MAX CB YORK INTERNATIONAL...
Page 37
YCWS0240SC YCWS0100SC YCWS0120SC YCWS0140SC YCWS0180SC YCWS0200SC YCWS0220SC YCWS0240SC YCWS0100SC YCWS0120SC YCWS0140SC YCWS0180SC YCWS0200SC YCWS0220SC YCWS0240SC YCWS0100SC YCWS0120SC YCWS0140SC YCWS0180SC YCWS0200SC YCWS0220SC YCWS0240SC YORK INTERNATIONAL SYSTEM #2 MAX DUAL MIN NF CIR. DUAL FUSE DISC SW FUSE MAX CB FORM 201.24-EG1...
Page 38
YCWS0100SC YCWS0120SC YCWS0140SC YCWS0180SC YCWS0200SC YCWS0220SC YCWS0240SC Cont (SEE FIG 10 & 11 , PAGE 30 & 31) in each motor control center.) MAX DUAL MIN N/F DUAL FUSE DISC SW FUSE MAX CB SYSTEM #1 SYSTEM #2 YORK INTERNATIONAL...
Page 41
This disconnect is not intended to be a Load Break Device. 9. Field Wiring by others which complies to the National Electrical Code & Local Codes. YORK INTERNATIONAL MULTIPOINT WIRING SYSTEM #2 N-F DIS SW...
Customer Wiring Data FIGURE 9 - MULTIPOINT POWER SUPPLY CONNECTION - STANDARD UNIT FIGURE 10 - SINGLE POINT POWER SUPPLY WITH INTERNAL CIRCUIT BREAKER OR NON-FUSED DISCONNECT SWITCH YORK INTERNATIONAL...
Page 43
LEGEND TERM BLOCK C.B. NF DISC SW D.F. DISC MIN NF Y-D LRA YORK INTERNATIONAL VOLTAGE CODE 17 = 200-3-60 28 = 230-3-60 40 = 380-3-60 46 = 460-3-60 58 = 575-3-60 TERMINAL BLOCK (FACTORY MOUNTED) CIRCUIT BREAKER (FACTORY MOUNTED)
Therefore the unit controls must not be modified without expressed written consent by YORK. The use of a simple switch or timer from a remote point is permitted; but it must be connected to the YORK unit panel at points expressly indicated for that purpose.
Guide Specifications YORK Model YCWS ______ Packaged Chiller(s). The (each) unit shall have a cooling capacity of ______ tons with Compressor kW when cooling GPM of water from ______ °F (°C) to ______ °F (°C) and with ____ GPM of condensing water entering at ____ °F (°C) and leaving...
Page 48
The power panel shall contain the compressor power terminals. U.L. recognized compressor motor starting contactors which meet l.E.C. requirements, current trans- former sensing for each compressor power source, for protection against under current, over current, imbal- anced current, single phasing compressor stall and voltage spikes. YORK INTERNATIONAL...