Automatic Initialization Of Linear Actuator - Siemens PROFIBUS PA SIPART PS2 Manual

Electropneumatic positioner for linear and rotary actuators
Hide thumbs Also See for PROFIBUS PA SIPART PS2:
Table of Contents

Advertisement

Preparing for Operation

3.6.2 Automatic initialization of linear actuator

.
68
If you can move the actuator correctly, leave it standing in a central po-
sition and start automatic initialization:
1.
Press the operation mode key
you to the Configuration operating mode.
Display:
2.
Switch to the second parameter by pressing the operation mode
key
briefly.
Display:
NOTE
It is vital that this value corresponds to the setting of the transmission
ratio selector (8, figure 2-1, page 24) (33° or 90°).
3.
Switch on to the following display with the operation mode key
You only need to set this parameter if you want to have the total
stroke in mm displayed at the end of the initialization phase. To do
this, select the same value in the display to which you have set the
carrier pin to the scale on the lever.
4.
Switch on to the following display with the operation mode key
for longer than 5 s. This brings
or
SIPART PS2 PA Manual
:
:
A5E00127926-03