Approved associated apparatus
or barrier
+
--
EEx
EEx
DP/PA coupling
Non-hazardous area
Figure 3-16
Electric connection of basic device with in intrinsically safe version
+
--
DP/PA coupling
Non-hazardous area
Figure 3-17
Electric connection for positioner in explosion-proof version or in type of explosion protection "n"
version
Safety position
SIPART PS2 PA Manual
A5E00127926-03
≤ 30 V
PROFIBUS PA
≤ 24 V
Hazardous area zone 1
≤ 30 V
≤ 32 V
PROFIBUS PA
The positioner is equipped with an additional input (terminal 81 [+] and
terminal 82 [--]) for driving to the safety position. After activating this
function this input must be supplied with uninterrupt +24 V, to allow nor-
mal positioning operation.
If this power supply is switched off or drops out, the air exhaust valve is
automatically opened and the drive will move to the pre-arranged safety
position, so that the drive cannot be activated using the keys on the
control unit or by means of the master switch. The communication with
the Master is still possible.
81
Input: Safe position
82
6
7
8
+
3 V
9
10
81
Input: Safe position
82
6
7
8
+
3 V
9
10
Hazardous area
Preparing for Operation
Positioner
Digital input 1
Positioner
Digital input 1
59