Scope of delivery
Technical data (continued)
Option modules
Electrical data
Ex protection to EN 50 014, EN 50 020 and 50 021
Mounting location
Permissible ambient temperature for operation
I
module
y
Direct current output for position feedback
(terminals 61/62)
Rated signal range i
Operating range
Power supply U
H
[k Ω ]
External load R
B
Transmission error
Temperature influence
Resolution
Residual ripple
Internal capacitance C
i
Internal inductance L
i
For connection to circuits with
Electrical isolation
Test voltage
NCS sensor
Positioning range
• Linear actuator
• Rotary actuator
Linearity (after correction by SIPART PS2)
• Linear actuator
• Rotary actuator
Hysteresis
Continuous operating temperature
Degree of housing protection
1
) Only in conjunction with the basic device 6DR5
146
Without Ex protection
-30 to +80 °C
(-22 to +176 °F)
6DR4004-8J (without Ex prot.) 6DR4004-6J (with Ex prot.)
+12 to 35 V
Only without Ex protection: -50 °C to +120 °C (-58 °F to +248 °F)with limited service life
7 7 7
-
7
E
7 7 7
. Only T4 permissible when using with Iy module.
With Ex protection
II 2G EEx ia/ib II C T4/T5/T6
Zone 1
1
T4: -30 to +80 °C
)
1
(T4: -22 to +176 °F
))
1
T5: -30 to +65 °C
)
1
(T5: -22 to +149 °F
))
1
T6: -30 to +50 °C
)
1
(T6: -22 to +122 °F
))
Two-wire system
4 to 20 mA, short-circuit-proof
3.6 to 20.5 mA
+ 12 to 30 V
≤ (U
[V] - 12 V) /i [mA]
H
≤ 0.3%
≤ 0.1%/10 K ( ≤ 0.1%/18 °F)
≤ 0.1%
≤ 1%
≤ 11 nF
Negligible
≤ 30 V DC
Intrinsically-safe: U
i
≤ 100 mA; P
≤ 1 W (only T4)
I
i
i
Electrically isolated from basic device
840 V DC, 1 s
max. 14 mm (max. 0.55 inch)
max. 120°
± 1%
± 1%
± 0.2%
-40 °C to +90 °C (-40 °F to +194 °F)
IP 68/NEMA 4x
SIPART PS2 PA Manual
1
) II 3G EEx nA L [L] II C T6
Zone 2
1
T4: -30 to +80 °C
)
1
(T4: -22 to +176 °F
))
1
T5: -30 to +65 °C
)
1
(T5: -22 to +149 °F
))
1
T6: -30 to +50 °C
)
1
(T6: -22 to +122 °F
))
6DR4004-6J (with Ex prot.)
+ 12 to 30 V
≤ 30 V DC
U
i
≤ 100 mA; P
≤ 1 W (only T4)
I
i
i
A5E00127926-03