Cyclic Data Transmission; Configuration; Configuring The User Data - Siemens PROFIBUS PA SIPART PS2 Manual

Electropneumatic positioner for linear and rotary actuators
Hide thumbs Also See for PROFIBUS PA SIPART PS2:
Table of Contents

Advertisement

5.3

Cyclic data transmission

5.3.1 Configuration

5.3.1.1

Configuring the user data

.
SIPART PS2 PA Manual
A5E00127926-03
Using cyclic data transmission, the user data relevant for process au-
tomation is transferred between the class 1 Master (control or automa-
tion system) and the positioner.
Information on the input and output range, as well as the consistency of
the cyclically transmitted data is defined in the DeviceMasterData file
(DMD file), tested with the device's configuration message and, if ap-
propriate, declared to be valid. During the design, the user data which
will be transmitted in cyclic operation is set. This means that it is pos-
sible to optimise the quantity of data to be transmitted. The DMD files
for all common devices are already stored in the Siemens control sys-
tem, however they are also accessible over the Internet
(www.ad.siemens.de/csi_e/gsd) and can be subsequently imported.
The user data which is made available to the control system or the
open-loop control via the PROFIBUS depends on the desired configu-
ration selected.
NOTE
For STEP 7, the configuring tool is HW-Konfig. For STEP 5, it is
COM_PROFIBUS.