Magis Pro V2 Internal Unit - Immergas SUPER TRIO Instructions And Warnings

Hide thumbs Also See for SUPER TRIO:
Table of Contents

Advertisement

1.7 CONNECTION WIRING
DIAGRAM SINGLE ZONE
HYDRONIC KIT (SECOND
ZONE OPTIONAL) AND
MAGIS PRO - MAGIS PRO
V2 INTERNAL UNIT.
Once the kit is assembled, proceed with
the wiring according to the diagram
Fig. 24.
- Connect the cables in the Magis Pro
- Magis Pro V2 Interna Unit control
panel following the connection dia-
gram in Fig. 30 - 31.
- Lower the wiring exiting the Magis
Pro - Magis Pro V2 Interna Unit until
it can be secured with the clips (1-2).
- Connect the storage tank probe
terminals (4) to the device terminal
24
4
block / terminal board (see wiring
diagram Fig. 30 - 31) and position it
on the storage tank in the appropriate
seat (Fig. 25), using the relative cable
clamp.
- Connect the flow probe connector
(10) to the wiring marked by the label
"SONDA" (PROBE), then connect the
wiring to the probe and connect the
"T-SIC" connector to the safety ther-
mostat (Only if the second optional
zone is present).
- Connect the connector with the red
"M-Z1" label to the pump / circulator
(7) and connect the wiring terminals
to the device terminal block / termi-
nal board (see wiring diagram Fig.
30 - 31).
1
2
6
5
9
10
21
- Connect the connector with the green
"M-Z2" label to the pump / circulator
(8) (Only if the second optional zone
is present).
- Connect the connector of the mixing
valve (6) marked with the "V.MISC"
(MIX.V) label (Only if the second
optional zone is present).
- Connect the antifreeze box connector
(9) to the wiring connector with the
"ANTIFREEZE" label, and connect
the wiring terminals to the device
terminal block / terminal board (see
wiring diagram Fig. 30 - 31).
- Make the connection to the power
supply of the Internal Unit using
the cable (3) as shown in the wiring
diagram (Fig. 30 - 31)
- Now group the various cables and join
them with the clip (5) supplied with
the hydraulic manifold.
Attention: in order for the probes to
function properly, before it is insert-
ed, it is recommended to put a bit
of conductive paste on the relative
probe-holder.
N.B.: wind the uncovered fittings with
the insulation present in the kit.
DHW probe - positioning (Det. 4)
3
25
7
8

Advertisement

Table of Contents
loading