Technical Specifications; Input; Output - Siemens SIPART PS100 Operating Instructions Manual

Electropneumatic positioners
Table of Contents

Advertisement

Technical specifications

10.1

Input

Analog input (AI), terminal 6 and 7
Nominal signal range
Minimum current to maintain the operation
Maximum load voltage
Static destruction limit
Digital input (DI), terminals 9 and 10
Galvanic isolation
Signal status 0, floating contact open
Signal status 1, floating contact closed
Contact load
10.2

Output

Analog output (AQ), terminals 61 and 62
Wiring configuration
Nominal signal range
Dynamic range I
O
Supply voltage U
H
External load R
[kΩ]
B
Resolution in relation to the nominal signal range
Transmission error in relation to the nominal signal range
Effect of ambient temperature
Maximum residual ripple
Galvanic isolation
Digital output (DQ), terminals 31 and 32
Maximum supply voltage U
Current consumption external, to be limited to
SIPART PS100
Operating Instructions, 11/2019, A5E45863537-AC
H
4 ... 20 mA
3.8 mA
6.5 V corresponds to 325 Ω at 20 mA
± 40 mA
Galvanically connected to analog input
Galvanically isolated from the outputs
> 300 kΩ
< 3 kΩ
Can only be used for floating contact;
Max. contact load < 20 μA, 3 V
2-wire connection
4 ... 20 mA
3.6 ... 20.5 mA
12 ... 30 V
≤ (U
[V] - 12 V)/I
[mA]
H
O
0.05%
± 0.3%
± 0.1%/10 C
± 0.5%
Galvanically isolated from the other electrical inputs and
outputs
35 V
50 mA
10
37