Connecting; Grounding - Siemens SIPART PS100 Operating Instructions Manual

Electropneumatic positioners
Table of Contents

Advertisement

Connecting

Lever for position detection
Danger of crushing and shearing with mounting kits which use a lever for position detection.
During commissioning and ongoing operation, severing or squeezing of limbs could occur as
a result of the lever. Risk of injury when working on control valves due to the high operating
force of the pneumatic actuator.
● Do not reach into the range of motion of the lever following mounting of the positioner and
Two-wire mode
NOTICE
Connection of voltage source to current input
Device damage if a voltage source is connected to the current input I
● Never connect the current input I
● Always use a high-impedance power source.
● Observe the static destruction limit specified in the "Input (Page 37)".
4.1

Grounding

The positioner is grounded via the mounting kit or via grounding with thread M4 on the
enclosure,
SIPART PS100
Operating Instructions, 11/2019, A5E45863537-AC
WARNING
mounting kit.
positioner may be destroyed.
in Overview of device components (Page 7).
to a low-resistance voltage source, otherwise the
w
4
(terminals 6 and 7).
w
17

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents