The following explains how to connect Ethernet wires to the inverter Ethernet terminal
block. These instructions replace pages 50-53 of the SolarEdge Installation Guide V2.0
and pages 72-75 of the SolarEdge Installation Guide North America V1.6.
1. Insert the Ethernet CAT5/6 cable through the appropriate communication
gland.
2. Remove the cable's external isolation using the crimping tool or cable cutter
and expose eight wires. Standard cables have eight wires (four twisted pairs), as
shown in the diagram below.
Figure 1: Preparing Connector Wiring
3. The inverter has an eight-pin terminal block connector for Ethernet
communication. Pull it out, as shown below:
Figure 2: Removing the Ethernet Terminal Block
SolarEdge Installation Guide, Errata
MAN-01-00092-1.0
1/2

Advertisement

loading

Summary of Contents for SolarEdge SE3000

  • Page 1 Errata The following explains how to connect Ethernet wires to the inverter Ethernet terminal block. These instructions replace pages 50-53 of the SolarEdge Installation Guide V2.0 and pages 72-75 of the SolarEdge Installation Guide North America V1.6. 1. Insert the Ethernet CAT5/6 cable through the appropriate communication gland.
  • Page 2 SolarEdge Installation Guide, Errata MAN-01-00092-1.0 4. Loosen the screws of the connectors on the Ethernet terminal block, aside for the screw of the G connector, as shown below: Screws Figure 3: Ethernet Block Terminal 5. Insert the ends of the wires into the connectors according to the table below:...