VICTRIX PRO 80 1 I -100 1 I - 120 1 I
43.2
Maximum nominal heat input
Maximum nominal effective output (80/60°C)
Maximum nominal effective output (50/30°C)
Minimum nominal heat input
Minimum nominal effective output (80/60°C)
Minimum nominal effective output (50/30°C)
Efficiency at 100% Pn (80/60°C)
Efficiency at 30% of the load (80/60°C)
Efficiency at 100% Pn (50/30°C)
Efficiency at 30% of the load (50/30°C)
Efficiency at 100% Pn (40/30°C)
Efficiency at 30% of the load (40/30°C)
Central heating circuit
Adjustable central heating system temperature
Max system operating temperature
Max system operating pressure
Available head with flow rate of 1000 l/h
Gas supply
Fan speed METHANE (G20)
Fan speed LPG (G31)
Gas flow rate to the burner METHANE (G20)
Gas flow rate to the burner LPG (G31)
Electric power supply
Nominal power absorption
Installed electric power
Power absorbed by fan
Power absorbed by pump
Electrical insulation rating
Boiler water capacity
Weight of empty boiler
TECHNICAL DATA
MIN - MAX
MIN - MAX
MIN - MAX
MIN - MAX
IP
VICTRIX PRO 120
kW (kcal/h)
114.1 (98.109)
kW (kcal/h)
111.0 (95.460)
kW (kcal/h)
121.7 (104.682)
kW (kcal/h)
11.4 (9.813)
kW (kcal/h)
11.0 (9.460)
kW (kcal/h)
12.2 (10.520)
%
97.3
%
100.4
%
106.7
%
107.1
%
107.2
%
107.1
°C
20-85
°C
90
bar
4.4
kPa (m H
O)
91.2 (9,30)
2
RPM
1200 - 7000
RPM
1150 - 6900
m
/h
1.21 - 12.07
3
kg/h
0.89 - 8.86
V/Hz
230 - 50
A
2.10
W
440
W
160
W
236
X5D
litres
11.7
kg
102.5
55