INDEX INDEX TABLE OF CONTENTS 1 VICTRIX PRO 35 1 I-55 1 I SPECIFICATIONS ..........................5 2 VICTRIX PRO 80 1 I-100 1 I-120 1 I SPECIFICATIONS ......................6 VICTRIX PRO 35 1 I-55 1 I MAIN PARTS ...........................7 4 VICTRIX PRO 80 1 I-100 1 I-120 1 I MAIN PARTS ........................8 5 VICTRIX PRO 35 1 I-55 1 I MAIN MEASUREMENTS .......................9 6 VICTRIX PRO 80 1 I MAIN MEASUREMENTS ........................10 7 VICTRIX PRO 100 1 I-120 1 I MAIN MEASUREMENTS......................11...
Page 4
With single or cascade installation, VICTRIX PRO 1 I can be ing and for cascade configuration (up to 5 appliances), with the combined with IMMERGAS solar solutions for the production advantage of guaranteeing higher overall output and reduced of domestic hot water, especially with storage tank units of 200, running costs.
• control panel supplied with P.C.B. with microprocessor with continuous flame modulation on heating with P.I.D. control, NOTA BENE: for correct installation of the boiler the Immergas modulation field referring to 50/30 °C between: "Green Range" air intake/fumes exhaust kit must be used and 3.7 and 37.3 kW (between 3.208 and 32.155 kcal/h) for...
8.1 to 80.3 kW (between 6.983 and 68.994 kcal/h) VICTRIX PRO 80 1 I; NOTA BENE: for correct installation of the boiler the Immergas 10.5 to 98.8 kW (between 9.023 and 84.942 kcal/h) "Green Range" air intake/fumes exhaust kit must be used and VICTRIX PRO 100 1 I;...
VICTRIX PRO 35 1 I - 55 1 I VICTRIX PRO 35 1 I-55 1 I MAIN PARTS KEY: 16 - Fumes hood - P.C.B. 17 - Manual air vent valve 18 - Condensation module - Gas valve 19 - Heat exchanger safety thermal fuse - Gas nozzle - Sleeve with seats for Venturi 20 - Burner...
VICTRIX PRO 80 1 I -100 1 I - 120 1 I VICTRIX PRO 80 1 I-100 1 I-120 1 I MAIN PARTS KEY: - Draining funnel. 15 - Ignition electrode - Gas cock 16 - Heat exchanger safety thermal fuse - Pump 17 - Detection electrode - Gas nozzle...
VICTRIX PRO 35 1 I - 55 1 I VICTRIX PRO 35 1 I-55 1 I MAIN MEASUREMENTS Model Height mm Width mm Depth mm VICTRIX PRO 35 1 I - 55 1 I CONNECTIONS Cover upper line SC = Condensate drain Ø 25 mm Distance between cover upper line and Distance between cover upper line and Ø...
VICTRIX PRO 80 1 I -100 1 I - 120 1 I VICTRIX PRO 80 1 I MAIN MEASUREMENTS Model Height mm Width mm Depth mm VICTRIX PRO 80 1 I 1038 CONNECTIONS Cover upper line SC = Condensate drain Ø 25 mm Distance between cover upper line and Distance between cover upper line and Ø...
VICTRIX PRO 80 1 I -100 1 I - 120 1 I VICTRIX PRO 100 1 I-120 1 I MAIN MEASUREMENTS Model Height mm Width mm Depth mm VICTRIX PRO 100 1 I-120 1 I 1038 CONNECTIONS Cover upper line SC = Condensate drain Ø...
Immergas S.p.a. declines all liability whenever the installer does with 4-bar safety valve and standard draining funnel). not use approved devices and Immergas original kits or uses There is a fitting for an expansion vessel on the flow and return them improperly.
Immergas S.p.a. declines all liability whenever the installer does with 4-bar safety valve and standard draining funnel). not use approved devices and Immergas original kits or uses There is a fitting for an expansion vessel on the flow and return them improperly.
Immergas declines all liability whenever the installer does not stub pipes. use original Immergas devices and kits, or uses them improperly. The sensitive elements of the safety devices must be set up as described in the installation instructions, in compliance with the provisions cascade forth in the ''R'' collection.
VICTRIX PRO 1 I 11 THREE-WAY VALVE KIT FOR COMBINATION WITH SEPARATE STORAGE TANK UNIT (CODE 3.023950) FOR VICTRIX PRO 35 1 I - 55 1 I - 80 1 I - 100 1 I - 120 1 I The kit is sized for single boiler operation or in combination any pre-installed temperature probe from the storage tank unit.
HYDRAULIC SEPARATOR KIT FOR INDIVIDUAL BOILER VICTRIX PRO 35 1 I - 55 1 I (CODE 3.023951) The hydraulic separator (compensator) is a particularly signif- The brass sludge collecting filter, with relative inspectable icant part inside the hydraulic circuits. stainless steel cartridge, protects the condensation module from It is an open manifold (2) which places system flow and return getting clogged with the sludge or build-up from the system.
VICTRIX PRO 80 1 I -100 1 I - 120 1 I HYDRAULIC SEPARATOR KIT FOR INDIVIDUAL BOILER VICTRIX PRO 80 1 I - 100 1 I - 120 1 I (CODE 3.023952) The hydraulic separator (compensator) is a particularly signif- The brass sludge collecting filter, with relative inspectable icant part inside the hydraulic circuits.
14 VICTRIX PRO 35 1 I - 55 1 I ADAPTER KIT IN REPLACEMENT OF THE PREVIOUS ONE RANGE OF WALL-HUNG BOILERS IN SINGLE CONFIGURATION (CODE 3.023966) 1 I models in place of the models from the previous range of This kit is composed of just two gaskets 44x34x2 (1) and two VICTRIX 50-75 wall-hung boilers in single configuration.
3.024038. The modular boilers, i.e. installed in cascade (battery) with an Im- Immergas declines all liability whenever the installer does not use mergas original hydraulic manifold kit, must be considered a unique original Immergas devices and kits, or uses them improperly.
3.024038. The modular boilers, i.e. installed in cascade (battery) with an Im- Immergas declines all liability whenever the installer does not use mergas original hydraulic manifold kit, must be considered a unique original Immergas devices and kits, or uses them improperly.
Page 21
3.024038. The modular boilers, i.e. installed in cascade (battery) with an Im- Immergas declines all liability whenever the installer does not use mergas original hydraulic manifold kit, must be considered a unique original Immergas devices and kits, or uses them improperly.
VICTRIX PRO 35 1 I - 55 1 I (CODE 3.023955) The modular boilers, i.e. appliances comprised of multiple boilers For design purposes, by installing the Immergas safety kit, the set up by the manufacturer to operate in cascade (battery) with...
VICTRIX PRO 80 1 I - 100 1 I - 120 1 I (CODE 3.023961) The modular boilers, i.e. appliances comprised of multiple boilers For design purposes, by installing the Immergas safety kit, the set up by the manufacturer to operate in cascade (battery) with...
VICTRIX PRO 1 I 19 HYDRAULIC SEPARATOR KIT MEASUREMENTS AND FITTINGS (OPTIONAL) The hydraulic separator (compensator) is a particularly signif- It is advisable to include a hydraulic compensator (1) every time icant part inside the hydraulic circuits. the overall flow rate required by the system is greater than what It is an open manifold (1) which places system flow and return the boiler is able to supply.
Page 25
VICTRIX PRO 1 I 19.1 HYDRAULIC SEPARATOR KIT FOR BOILERS UP TO 100 KW WITH THREADED CONNECTIONS G 2 1/2" (CODE 3.020839) KEY: - Vent valve - Shut-off valve - Probe fitting (not supplied) - Hydraulic separator (12 litre capac- ity) - Draining valve 19.2 HYDRAULIC SEPARATOR KIT FOR BOILERS IN CASCADE CONFIGURATION...
Page 26
VICTRIX PRO 1 I 19.3 HYDRAULIC SEPARATOR KIT FOR BOILERS IN CASCADE CONFIGURATION UP TO 350 KW FLANGED CONNECTIONS DN 100 (CODE 3.023965) KEY: - Vent valve - Shut-off valve - Probe fitting (not supplied) - Hydraulic separator (42 litre capac- ity) - Draining valve 19.4 HYDRAULIC SEPARATOR KIT FOR BOILERS IN CASCADE CONFIGURATION...
Page 27
VICTRIX PRO 1 I 19.5 HYDRAULIC SEPARATOR KIT FOR BOILERS IN CASCADE CONFIGURATION UP TO 600 KW FLANGED CONNECTIONS DN 100 (CODE 3.023962) KEY: - Vent valve - Shut-off valve - Probe fitting (not supplied) - Hydraulic separator (85 litre capacity) - Draining valve...
VICTRIX PRO 1 I 20 "FREE STANDING" SUPPORTING FRAME KIT (CODE 3.024246) FOR VICTRIX PRO 1 I VICTRIX PRO 1 I can also be installed on a specific modular on the number of boilers that need to be installed. The frame supporting frame which offers single or cascade installation has supporting collars for the hydraulic manifolds and can be (up to 5 boilers), in linear set-up, or back-to-back for more...
VICTRIX PRO 35 1 I - 55 1 I KIT SIZES AND CONNECTIONS (OPTIONAL) WITH VICTRIX PRO 35 1 I - 55 1 I BOILERS WITH INSTALLATION ON SUPPORTING FRAME SET UP IN LINE (UP TO A MAXIMUM OF FIVE APPLIANCES)
Page 30
21.1 KIT SIZES AND CONNECTIONS (OPTIONAL) WITH VICTRIX PRO 35 1 I - 55 1 I BOILERS WITH INSTALLATION ON SUPPORTING FRAME SET UP BACK-TO-BACK (UP TO A MAXIMUM OF FIVE APPLIANCES)
VICTRIX PRO 80 1 I -100 1 I - 120 1 I 22 KIT SIZES AND CONNECTIONS (OPTIONAL) WITH VICTRIX PRO 80 1 I - 100 1 I - 120 1 I BOILERS WITH INSTALLATION ON SUPPORTING FRAME SET UP IN LINE (UP TO A MAXIMUM OF FIVE APPLIANCES)
Page 32
VICTRIX PRO 80 1 I -100 1 I - 120 1 I 22.1KIT SIZES AND CONNECTIONS (OPTIONAL) WITH VICTRIX PRO 80 1 I - 100 1 I AND 120 1 I BOILERS WITH INSTALLATION ON SUPPORTING FRAME SET UP BACK-TO-BACK (UP TO A MAXIMUM OF FIVE APPLIANCES)
VICTRIX PRO 35 1 I - 55 1 I GRAPH OF VICTRIX PRO 35 1 I - 55 1 I PUMP HEAD FLOW RATE The VICTRIX PRO 35 1 I - 55 1 I boilers are supplied with a at maximum speed. built-in circulation pump with 3-position electric speed control.
VICTRIX PRO 80 1 I -100 1 I - 120 1 I GRAPH OF VICTRIX PRO 80 1 I PUMP HEAD FLOW RATE The VICTRIX PRO 80 1 I boilers are supplied with a built-in (single pipe and module) it is recommended to use the pump circulation pump with 3-position electric speed control.
VICTRIX PRO 80 1 I -100 1 I - 120 1 I GRAPH OF VICTRIX PRO 100 1 I PUMP HEAD FLOW RATE The VICTRIX PRO 100 1 I boilers are supplied with a built-in (single pipe and module) it is recommended to use the pump circulation pump with 3-position electric speed control.
VICTRIX PRO 80 1 I -100 1 I - 120 1 I GRAPH OF VICTRIX PRO 120 1 I PUMP HEAD FLOW RATE The VICTRIX PRO 120 1 I boilers are supplied with a built-in (single pipe and module) it is recommended to use the pump circulation pump with 3-position electric speed control.
VICTRIX PRO 1 I FEED WATER TREATMENT Treating the supply water allows you to prevent problems and - for all systems, it is necessary to provide chemical condition- maintain the functionality and efficiency of the generator ing. For systems of > 350 kW it is necessary to install a safety over time.
VICTRIX PRO 1 I EXAMPLE OF DIRECT CONTROL WITHOUT CASCADE REGULATOR KIT INAIL OF A BOOSTER PUMP AND A COMMON FLOW PROBE FUNCTION AVAILABLE FOR THE 2ND SEMESTER OF 2014 System flow probe for boiler code 3.024245 INAIL Electrical connection diagram for probes and pumps External Relay (Optional) KEY:...
VICTRIX PRO 1 I 31 EXAMPLE OF SIMPLE CASCADE, WITHOUT INCLUDING THE CASCADE REGULATOR (2 BOILER MAXIMUM) FUNCTION AVAILABLE FOR THE 2ND SEMESTER OF 2014 BUS connection for operation in simple cascade INAIL This application can only be used in combination with a maximum of 2 boilers with the same output (in fact, while the cascade regulator - through fan rpm detection - rises and acts on the output delivered by the boilers, with simple cascade it is...
VICTRIX PRO 80 1 I -100 1 I - 120 1 I VICTRIX PRO 80 1 I - 100 1 I AND 120 1 I HYDRAULIC DIAGRAM KEY: 14 - Air sample point - Draining funnel on view 15 - Flue sample point - 4 bar safety valve 16 - Condensing module air vent valve - Boiler draining valve...
80/125 kits can be used. Installed in cascade configuration inside the heating control For correct installation of the boiler, the particular Immergas units or technical rooms, it is possible to use the relevant pro- "Green" range air intake/fumes exhaust kits must be used as...
VICTRIX PRO 1 I Ø 80/125 CONCENTRIC HORIZONTAL KIT (CODE 3.015242) THE KIT INCLUDES: 1 - N° 1 Adapter Ø 80/125 2 - N° 1 Gasket Detail (3) is as per standard with the boiler 4 - N° 1 Ø 80/125 87° concentric bend 5 - N°...
VICTRIX PRO 1 I Ø 80/125 CONCENTRIC VERTICAL KIT (CODE 3.015243) Ø 80/125 VERTICAL KIT MAXIMUM LENGTH ACCEPT- Vertical metres (including terminal) VICTRIX PRO 35 1 I = 11.5 m VICTRIX PRO 55 1 I = 18 m VICTRIX PRO 80 1 I = 15 m VICTRIX PRO 100 1 I = 11 m VICTRIX PRO 120 1 I = 6 m THE KIT INCLUDES:...
VICTRIX PRO 80 1 I -100 1 I - 120 1 I FLUE EXHAUST MANIFOLD KIT Ø 200 WITH FLUE ADJUSTING DEVICES VICTRIX PRO 80 1 I - 100 1 I - 120 1 I (CODE 3.024281) THE KIT INCLUDES: 1 - Connection for 1st Boiler 2 - Connection for 2nd Boiler 3 - Clapet DN125...
VICTRIX PRO 80 1 I -100 1 I - 120 1 I FLUE EXHAUST MANIFOLD KIT Ø 250 WITH FLUE ADJUSTING DEVICES FOR EXPANSION OF 4 VICTRIX PRO 100 1 I - 120 1 I (CODE 3.024666) THE KIT INCLUDES: 3 - Clapet DN125 7 - Drain trap unit 9 - Manifold for 4th Boiler DN250...
VICTRIX PRO 1 I Ø 80 FLEXIBLE DUCTING SYSTEM The Immergas Ø 80 mm system for flexible ducting of existing chimneys is made up from a series of components, identified as individual kits, which can be assembled depending on the specific installation requirements.
COMBUSTION CHARACTERISTICS FOR VICTRIX PRO 35 1 I Methane (G20) LPG (G31) Combustion efficiency 100% Pn (80/60°C) 98.4 98.4 Combustion efficiency P min (80/60°C) 98.4 98.4 Effective efficiency at 100% Pn (80/60°C) 97.3 97.3 Effective efficiency P min (80/60°C) 86.3 86.3 Effective efficiency at 100% Pn (50/30°C) 107.0...
Page 57
VICTRIX PRO 35 1 I - 55 1 I 44.1 COMBUSTION CHARACTERISTICS FOR VICTRIX PRO 55 1 I Methane (G20) LPG (G31) Combustion efficiency 100% Pn (80/60°C) 98.2 98.2 Combustion efficiency P min (80/60°C) 98.3 98.3 Effective efficiency at 100% Pn (80/60°C) 97.3 97.3 Effective efficiency P min (80/60°C)
Page 58
VICTRIX PRO 80 1 I -100 1 I - 120 1 I 44.2 COMBUSTION CHARACTERISTICS FOR VICTRIX PRO 80 1 I Methane (G20) LPG (G31) Combustion efficiency 100% Pn (80/60°C) 97.8 97.8 Combustion efficiency P min (80/60°C) 98.6 98.6 Effective efficiency at 100% Pn (80/60°C) 97.0 97.0 Effective efficiency P min (80/60°C)
Page 59
VICTRIX PRO 80 1 I -100 1 I - 120 1 I 44.3 COMBUSTION CHARACTERISTICS FOR VICTRIX PRO 100 1 I Methane (G20) LPG (G31) Combustion efficiency 100% Pn (80/60°C) 98.1 98.1 Combustion efficiency P min (80/60°C) 98.5 98.5 Effective efficiency at 100% Pn (80/60°C) 97.5 97.5 Effective efficiency P min (80/60°C)
Page 60
VICTRIX PRO 80 1 I -100 1 I - 120 1 I 44.4 COMBUSTION CHARACTERISTICS FOR VICTRIX PRO 120 1 I Methane (G20) LPG (G31) Combustion efficiency 100% Pn (80/60°C) 98.0 98.0 Combustion efficiency P min (80/60°C) 98.4 98.4 Effective efficiency at 100% Pn (80/60°C) 97.3 97.3 Effective efficiency P min (80/60°C)
VICTRIX PRO 1 I OPTIONAL Hydraulic type of kit Safety devices kit for individual boiler IPX4D protection box kit safety devices kit code 3.023949 for individual boiler code 3.024028 Safety devices kit G 2 1/2" for Safety devices kit DN 100 for VICTRIX PRO 80 1 I VICTRIX PRO 35 1 I-55 1 I in cascade configuration 100 1 I-120 1 I in cascade configuration code 3.023955...
Page 62
VICTRIX PRO 1 I Kit for heat adjustment Cascade and zone regulator kit Support kit for fixing the regulator to the wall code 3.015244 code 3.015265 Zone manager kit Modulating room thermostat kit code 3.015264 code 3.015245 External probe kit External probe kit for connection to the boiler for connection to the cascade and zone regulator...
VICTRIX PRO 1 I HEAT ADJUSTMENT APPENDIX HEAT ADJUSTMENT SYSTEMS (OPTIONAL) System heating. relevant kits, available in the 200, 300, 500, 1000, 1500 and 2000 litre versions. The Storage Tank units are equipped with double Individual modular boilers or installed in cascade configuration, require a suitable heat adjustment system able to communicate coil for heat exchange.
VICTRIX PRO 1 I CASCADE AND ZONE REGULATOR (CODE 3.015244) The cascade and zones regulator allows to manage, control and program the functioning sequence of the connected boilers. It can be cascade and programmed via parameters that allow to guarantee ideal temperature conditions at all times of the day and night for each individual day of the week, both for the C.H.
VICTRIX PRO 1 I CASCADE AND ZONE REGULATOR DIAGRAM OF CONNECTIONS AND TERMINALS There are terminal blocks on the back of the cascade and zone Some parts belonging to the heating control unit must be con- regulator dedicated to the network connections and the low nected to the respective terminal blocks.
VICTRIX PRO 1 I CASCADE AND ZONE REGULATOR / ZONE MANAGER PUSH BUTTON PANEL AND DISPLAY AND CONTROL SCREEN VICTRIX PRO 1 I zone manager VICTRIX PRO 1 I cascade and zone regulator KEY: 1 - Selection and confirmation knob 2 - Required daytime room temperature 3 - Required night-time room temperature 4 - Required D.H.W.
VICTRIX PRO 1 I ZONE MANAGER (CODE 3.015264) In addition to the functions described for the cascade heat adjuster, the cascade regulator allows to control all the im- portant information regarding operation of the appliance and the heating system with the opportunity of easily intervening on the previously set parameters without having to go to the place where the cascade regulator is installed.
VICTRIX PRO 1 I MODULATING ROOM THERMOSTAT (CODE 3.015245) The modulating room thermostats (not traditional On/Off) functions only when coupled wit the cascade regulator and allows regulation of the room temperature of one of the zones into which the plant is divided (both in individual and cascade installation).
VICTRIX PRO 1 I EXTERNAL PROBE TO CONNECT TO THE BOILER (CODE 3.015266) The external probe allows to decrease or increase the max. flow temperature to the system when the external temperature in- creases or decreases, in order to adjust the heat supplied to the system according to the change in external temperature.
VICTRIX PRO 1 I KIT FOR REMOTE MANAGEMENT (CODE 3.024244) (EXCLUSIVELY IN COMBINATION WITH THE CASCADE AND ZONE REGULATOR) Using the remote management kit it is possible to control the single boiler or cascade of boilers remotely. The remote man- agement kit only works in combination with Cascade and zone regulator code 3.015244, which requires software version 3.0 or later (the software version of the cascade and zone regulator...
Page 72
VICTRIX PRO 1 I 1 Registration screen. Enter the username in the upper field and the password in the lower field. N.B.: with direct connections (i.e. Ethernet, and NOT through the Internet) the pre-defined username and password that need to be entered in the window are: - Username: “EBV”...
Page 73
VICTRIX PRO 1 I 4 Setting central heating parameters. The window to cascade these parameters automatically opens when you click on a variable/editable parameter. The parameters can be edited by clicking on the symbols “+” or “-”. Click on “Prog” to store the set value. Press “Esc” to exit the setting mode and close the window.
Each system needs to be accurately sized by a professional; Immergas will not be held liable for the failure to have a certified engineer inspect the project, who is also required to practice with good technique and in accordance with regulations in force.
Page 75
VICTRIX PRO 1 I 54.1 EXAMPLE SYSTEM WITH VICTRIX PRO 1 I IN SINGLE CONFIGURATION...
Page 76
VICTRIX PRO 1 I 54.2 EXAMPLE OF PLANT ENGINEERING FOR VICTRIX PRO IN CASCADE CONFIGURATION...
Page 77
VICTRIX PRO 1 I 54.3 EXAMPLE OF PLANT ENGINEERING FOR VICTRIX PRO IN CASCADE CONFIGURATION...
Page 79
During the useful life of the products, performance is affected by external factors, such as the hardness of the D.H.W., atmos- pheric agents, deposits in the system and so on. The declared data refers to new products that are correctly installed and used in accordance with applicable regulations. N.B.: correct periodic maintenance is highly recommended.
Page 80
Follow us on Immergas Italia immergas.com To request further specific details, sector Professionals can also use the following e-mail address: consulenza@ immergas.com Immergas S.p.A. 42041 Brescello (RE) - Italy Tel. 0522.689011 Fax 0522.680617 QUALITY SYSTEM CERTIFIED UNI EN ISO 9001:2008...