2.3 Limit Values - Siemens SITRANS VP300 Operating Instructions Manual

Electropneumatic positioners with or without hart
Hide thumbs Also See for SITRANS VP300:
Table of Contents

Advertisement

Operate
6.2 Parameter description
6.2.2.3

"2.3 Limit values"

Use this menu to set the alarm limits and the direction of action of these limits.
"2.3.1 A1 Alarm limit"
Factory setting:
Setting range:
Purpose:
Description:
"2.3.2 A1 Direction of action"
Factory setting:
Setting options:
Purpose:
"2.3.3 A2 Alarm limit"
Factory setting:
Setting range:
Purpose:
Description:
"2.3.4 A2 Direction of action"
Factory setting:
Setting options:
Purpose:
82
10.0 %
0.0 ... 100.0 %
Specifying the response threshold for Alarm A1.
Use this parameter to set the point as of which an alarm is to be
signaled. The response thresholds for alarms refer to the mechanical
travel as determined in initialization.
Off
 Off
 Min
 Max
Adapting whether a message is to be issued if the alarm limit is fallen
below (Min) or exceeded (Max).
90.0 %
0.0 ... 100.0 %
Specifying the response threshold for Alarm A2.
Use this parameter to set the point as of which an alarm is to be
signaled. The response thresholds for alarms refer to the mechanical
travel as determined in initialization.
Off
 Off
 Min
 Max
Adapting whether a message is to be issued if the alarm limit is
fallen below (Min) or exceeded (Max).
SITRANS VP300 with or without HART
Operating Instructions, 03/2011, A5E01258666-03