Pneumatic Connection In The Flameproof Enclosure - Siemens SIPART PS2 Compact Operating Instructions

Electropneumatic positioners with and without hart
Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

4.3.2

Pneumatic connection in the flameproof enclosure

Structure
The pneumatic connections are provided on the right side of the positioner.
Restrictor Y2
*)
Restrictor Y1
Actuating pressure Y2
Supply air P
Z
*) for double-acting actuators
Figure 4-12
Pneumatic connection in the flameproof enclosure
4.4
Restrictors
● Reduce the air output to achieve actuating times of T > 1.5 s for small actuators. Use restrictors Y1
purpose.
● When turned clockwise, they reduce the air output and finally shut it off.
● In order to set the restrictors, we recommend closing them and then opening slowly.
● In case of double-acting valves, ensure that both restrictors have approximately the same setting.
Restrictor Y1
Restrictor Y2, only in the version for double-acting actuators
Hexagon socket-head screw 2.5 mm
Figure 4-13
Restrictors
22
*)
Actuating pressure Y1
Exhaust air outlet
Enclosure ventilation (2x)
and Y2
for this
SIPART PS2 (6DR5...)
A5E03436620-04, 02/2014