4.5.1.3

Opening the device version with "flameproof enclosure"

Overview screen
Risk of explosion
Before supplying the positioner with auxiliary power in potentially hazardous areas, ensure the
following:
● The installed electronic unit has been approved.
● The enclosure of the positioner is closed.
● The duct openings for electronic connections must be closed. Only use the Ex d certified
● If you use a "conduit piping system", install an ignition trap. The maximum distance
SIPART PS2 with 4 to 20 mA/HART
Operating Instructions, 11/2019, A5E00074631-AE
DANGER
cable entries or sealing plugs.
between the ignition trap and the positioner enclosure is 46 cm (18 inch).
Installing/mounting
4.5 Installing option modules