Diagnostic Value '59.Ma - Setpoint Current; Diagnostic Value '60.Pz Supply Pressure (Pz); Diagnostic Value '63.Pzmax Supply Pressure (Pz) Min/Max Pointer; Diagnostic Value '64.N_Min Event Counter - Siemens SIPART PS2 Series Operating Instructions Manual

Electropneumatic positioners with 4 to 20 ma/hart
Hide thumbs Also See for SIPART PS2 Series:
Table of Contents

Advertisement

Diagnostics and troubleshooting
11.2 Diagnostics
11.2.4.35

Diagnostic value '59.mA - Setpoint current'

Here you can display the current setpoint in mA.
11.2.4.36

Diagnostic value '60.PZ Supply pressure (PZ)'

Indication on the display: ##.### (bar)
Purpose:
11.2.4.37

Diagnostic value '63.PZMAX Supply pressure (PZ) min/max pointer

Indication on the display: ##.### (bar)
Purpose:
11.2.4.38

Diagnostic value '64.N_MIN Event counter'

Display range:
Purpose:
228
###.## (psi)
#.#### (MPa)
Shows the current supply pressure PZ. The value refers to the
pressure unit assigned in "U1.PUNIT (Page 188)".
If the supply pressure PZ is switched off, the pressure value shown
in the display is 0. Depending on the height at which you use the
positioner, the displayed pressure value is ≠0. Press the
for at least 5 seconds to set the value to 0. "reset" is shown in the
display for as long as you press the
only possible if the displayed pressure value is in the range -0.5 to
+0.5 bar.
###.## (psi)
#.#### (MPa)
The supply pressure (PZ) is continuously monitored and the maxi‐
mum value (min/max pointer) is displayed.
The min/max pointer can be reset via HART communication.
0 ... 99999
Each new measured value of the pressure monitoring is compared
with the value set in "U.PZLIM (Page 188)". The counter increases
when the supply pressure is lower than the configured limit value.
The counter can be reset via HART communication.
button. This calibration is
SIPART PS2 with 4 to 20 mA/HART
Operating Instructions, 11/2019, A5E00074631-AE
button

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents