Diagnostics Value '15.Devi - Dynamic Control Valve Behavior; Diagnostic Value '16.Onlk - Pneumatic Leakage; Diagnostic Value '17.Stic - Stiction (Slipstick); Diagnostic Value '18.Zero - Lower Endstop - Siemens SIPART PS2 Series Operating Instructions Manual

Electropneumatic positioners with 4 to 20 ma/hart
Hide thumbs Also See for SIPART PS2 Series:
Table of Contents

Advertisement

Diagnostics and troubleshooting
11.2 Diagnostics
11.2.4.14

Diagnostics value '15.DEVI - Dynamic control valve behavior'

Requirement:
Display range:
Purpose:
11.2.4.15

Diagnostic value '16.ONLK - Pneumatic leakage'

Requirement:
Display range:
Purpose:
11.2.4.16

Diagnostic value '17.STIC - Stiction (slipstick)'

Requirement:
Display range:
Purpose:
11.2.4.17

Diagnostic value '18.ZERO - Lower endstop'

Requirement:
Display range:
Purpose:
220
Monitoring of dynamic control valve behavior 'b.\\DEVI' (Page 168)
parameter is activated.
0.0 ... 100.0
This value in percent provides information about the current dynam‐
ically determined deviation from the model response.
Monitoring/compensation of pneumatic leakage 'C.\\LEAK'
(Page 170) parameter is activated.
0 ... 100
This diagnostics parameter shows the current leakage indicator.
Monitoring of stiction (slipstick) 'd.\\STIC' (Page 173) parameter is
activated.
0.0 ... 100.0
This diagnostics parameter shows the filtered value of the slip
jumps in percent resulting from the stiction.
Monitoring of lower endstop 'F.\\ZERO' (Page 176) parameter is
activated.
'39.YCLS' Tight closing/fast closing with manipulated variable
(Page 153) Parameter is set to one of the following values: 'do', 'uP
do', 'Fd', 'Fu Fd', 'uP Fd', 'Fu do'
0.0 ... 100.0
Indication of how many percent the lower endstop has changed
compared to its value during initialization.
SIPART PS2 with 4 to 20 mA/HART
Operating Instructions, 11/2019, A5E00074631-AE

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents