Siemens SIPART PS2 Series Operating Instructions Manual page 214

Electropneumatic positioners with 4 to 20 ma/hart
Hide thumbs Also See for SIPART PS2 Series:
Table of Contents

Advertisement

Diagnostics and troubleshooting
11.2 Diagnostics
No.
Short desig‐
Meaning
nation
23
IMPUP
Pulse length up
24
IMPDN
Pulse length down
25
PAUTP
Pulse pause
26
DBUP
Deadband up
27
DBDN
Deadband down
28
SSUP
Slow step zone up
29
SSDN
Slow step zone down
30
TEMP
Current temperature
31
TMIN
Minimum temperature (min/max pointer)
32
TMAX
Maximum temperature (min/max pointer)
33
T1
Number of operating hours in temperature range 1
34
T2
Number of operating hours in temperature range 2
35
T3
Number of operating hours in temperature range 3
36
T4
Number of operating hours in temperature range 4
37
T5
Number of operating hours in temperature range 5
38
T6
Number of operating hours in temperature range 6
39
T7
Number of operating hours in temperature range 7
40
T8
Number of operating hours in temperature range 8
41
T9
Number of operating hours in temperature range 9
42
VENT1
Number of switching cycles pneumatic block, Valve 1 0 ... 4.29E9
43
VENT2
Number of switching cycles pneumatic block, Valve 2 0 ... 4.29E9
44
VEN1R
Number of switching cycles pneumatic block, Valve 1,
resettable
45
VEN2R
Number of switching cycles pneumatic block, Valve 2,
resettable
46
STORE
Save the current values as 'last maintenance'
(press
47
PRUP
Prediction up
48
PRDN
Prediction down
49
WT00
Number of operating hours in the travel range WT00
50
WT05
Number of operating hours in the travel range WT05
51
WT10
Number of operating hours in the travel range WT10
52
WT30
Number of operating hours in the travel range WT30
53
WT50
Number of operating hours in the travel range WT50
54
WT70
Number of operating hours in the travel range WT70
55
WT90
Number of operating hours in the travel range WT90
56
WT95
Number of operating hours in the travel range WT95
57
LKPUL
Length of the leakage compensation pulse
58
LKPER
Period of the leakage compensation pulse
214
button for 5 seconds)
Representable di‐
Unit
agnostics values
6 ... 160
ms
6 ... 160
ms
2 ... 28 ... 320
ms
0.1 ... 10.0
%
0.1 ... 10.0
%
0.1 ... 10.0 ...
%
100.0
0.1 ... 10.0 ...
%
100.0
-50 ... 100
°C
-58 ... 212
°F
-50 ... 100
°C
-58 ... 212
°F
-50 ... 100
°C
-58 ... 212
°F
0 ... 4.29E9
Hours
0 ... 4.29E9
Hours
0 ... 4.29E9
Hours
0 ... 4.29E9
Hours
0 ... 4.29E9
Hours
0 ... 4.29E9
Hours
0 ... 4.29E9
Hours
0 ... 4.29E9
Hours
0 ... 4.29E9
Hours
-
-
0 ... 4.29E9
-
0 ... 4.29E9
-
-
-
1 ... 40
-
1 ... 40
-
0 ... 4.29E9
Hours
0 ... 4.29E9
Hours
0 ... 4.29E9
Hours
0 ... 4.29E9
Hours
0 ... 4.29E9
Hours
0 ... 4.29E9
Hours
0 ... 4.29E9
Hours
0 ... 4.29E9
Hours
-256 ... 0 ... 254
ms
0.00 ... 600.00
s
SIPART PS2 with 4 to 20 mA/HART
Operating Instructions, 11/2019, A5E00074631-AE
Properties

Hide quick links: