Siemens SIPART PS2 Series Operating Instructions Manual page 208

Electropneumatic positioners with 4 to 20 ma/hart
Hide thumbs Also See for SIPART PS2 Series:
Table of Contents

Advertisement

Diagnostics and troubleshooting
11.1 Output of system messages in the display
Messages during initialization
Message
Line
Up
Down
P---
X
RUN 1
X
RUN 2
X
RUN 3
X
RUN 4
X
RUN 5
X
YEND1
X
YEND2
X
RANGE
X
ok
x
RUN 1 /
X
ERROR
208
Meaning/cause
Measuring range was exceeded, the potenti‐
ometer is in the inactive zone, the transmis‐
sion ratio selectors or the effective lever arm
are not adjusted as per the actuator travel
Initialization was started, part 1 is active (the
direction of action is determined)
Initialization part 2 is active (actuator travel
check and determination of stops)
Initialization part 3 is active (determination
and display of travel times)
Initialization part 4 is active (determination of
the minimum controller increment length)
Initialization part 5 is active (optimization of
the transient response)
The first position of the stop can be approach‐
ed only in case of a manual initialization
The second position of the stop can be ap‐
proached only in case of a manual initialization
The position of the stop or the measuring
span is beyond the permissible measuring
range only in case of a manual initialization
The permissible measuring range of end po‐
sitions is achieved only in case of a manual
initialization
Error in "RUN 1", no movement e.g. due to the
lack of compressed air
Measure
● Switch the transmission ratio selector to
90°, especially in the case of part-turn ac‐
tuators.
● Adjust the effective lever length of linear
actuators as per the measuring range.
● Wait.
● Wait.
● Wait.
● Wait.
● Wait until "FINSH" is displayed. Initializa‐
tion was completed successfully.
1. Approach first position of the stop with the
button
or
.
2. Acknowledge using
1. Approach second position of the stop with
the button
or
.
2. Acknowledge using
● Approach a different position of the stop
using
or
button and acknowledge
using
button.
● Move the friction clutch until "ok" is dis‐
played, and then acknowledge with the
button.
● Terminate the initialization process using
the
button, switch to the P-manual
mode, and correct the actuator travel and
the position displacement sensor.
● Use the
button to acknowledge; the re‐
maining steps ("RUN 1" to "FINSH") run
automatically.
Possible causes:
● Insufficient supply of compressed air.
● Restrictor(s) blocked.
● Actuator does not move freely.
Measures:
1. Eliminate possible causes.
2. Restart initialization.
SIPART PS2 with 4 to 20 mA/HART
Operating Instructions, 11/2019, A5E00074631-AE