Parameter assignment
8.4 Description of parameters
8.4.3.13

Pressure monitoring 'U.\\PRES'

U. PRES - Activate pressure monitoring
Requirement:
Possible settings:
Purpose:
Factory setting:
U1.PUNIT - Pressure unit
Possible settings:
Purpose:
Factory setting:
U2.PZLIM - Low limit of the supply pressure (PZLIM)
Possible settings:
Purpose:
Factory setting:
U3.PZHYS - Hysteresis of the low limit of the supply pressure
Possible settings:
Purpose:
Factory setting:
188
The parameter "XDIAG (Page 162)" is set to "On1", "On2" or "On3".
● OFF
● On
Activates or deactivates all pressure-based diagnostics.
On
bar / psi / MPa
Defines the pressure unit for all pressure-based diagnostic param‐
eters.
bar
1.4 to 7.0 (bar)
20.30 ... 101.52 psi
0.140 ... 0.700 MPa
Defines the minimum required supply pressure.
When the value is undershot, the message "18 (Page 234)" ap‐
pears on the display in "Automatic" and "Manual" modes.
1.4
0.2 to 1.0 (bar)
2.90 ... 14.50 psi
0.020 ... 0.100 MPa
Defines the hysteresis of the low limit of the supply pressure
(U2.PZLIM).
The error message 18 (Page 234) in the "Automatic" and "Manual"
modes is deleted when the value of the supply pressure PZ is
"PZHYS" larger than the value assigned in "U2.PZLIM". The control
becomes active again if the configured fault reaction was "HOLd".
0.2
SIPART PS2 with 4 to 20 mA/HART
Operating Instructions, 11/2019, A5E00074631-AE