Monitoring The Upper Limit Temperature 'J.\\Tmax; J2.Levl1 - Threshold 1 - Siemens SIPART PS2 Series Operating Instructions Manual

Electropneumatic positioners with 4 to 20 ma/hart
Hide thumbs Also See for SIPART PS2 Series:
Table of Contents

Advertisement

8.4.3.9

Monitoring the upper limit temperature 'J.\\TMAX'

J. TMAX - Monitoring the upper limit temperature
Requirement:
Possible settings:
Purpose:
Factory setting:
J1.TUNIT - temperature unit
Possible settings:
Purpose:
Factory setting:

J2.LEVL1 - threshold 1

Adjustment range:
Purpose:
Factory setting:
SIPART PS2 with 4 to 20 mA/HART
Operating Instructions, 11/2019, A5E00074631-AE
The '52.XDIAG' Activating for extended diagnostics (Page 162) pa‐
rameter is set to 'On1', 'On2' or 'On3'.
● OFF
● On
The current temperature inside the enclosure of the field device is
recorded by a sensor on the basic electronics. Use this parameter
to activate continuous monitoring of the upper limit temperature
inside the enclosure. Monitoring is performed in three steps. To
activate monitoring, set the parameter to 'On'. Sub-parameters are
displayed. Appropriately set the sub-parameters.
The value is displayed in Diagnostic value '31.TMIN - Minimum
temperature' / '32.TMAX - Maximum temperature' (Page 224). The
positioner triggers a message if the current value exceeds one of
the three thresholds.
OFF
°C
°F
Use this sub-parameter to set the temperature unit '°C' or '°F'. The
selected temperature unit is then also applicable for all other tem‐
perature-based parameters.
°C
-40.0C ... 90.0C
-40.0F ... 194.0F
Use this sub-parameter to set the temperature for threshold 1.
The positioner triggers a threshold 1 message if the current tem‐
perature inside the enclosure exceeds threshold 1. This message is
only output if threshold 2 or 3 is not exceeded at the same time. The
process to activate and display this message is described in the
'XDIAG' parameter.
75.0C
Parameter assignment
8.4 Description of parameters
181

Hide quick links:

Advertisement

Table of Contents
loading