Prst' Preset; Pneum' Pneumatics Type - Siemens SIPART PS2 Series Operating Instructions Manual

Electropneumatic positioners with 4 to 20 ma/hart
Hide thumbs Also See for SIPART PS2 Series:
Table of Contents

Advertisement

Parameter assignment
8.4 Description of parameters
8.4.2.20

'50.PRST' Preset

Possible settings:
Purpose:
Description:
Factory setting:
See also
Display of diagnostics values (Page 212)
8.4.2.21

'51.PNEUM' Pneumatics type

Requirements:
Possible settings:
160
● ALL
● Init
● PArA
● diAg
Use this parameter to restore the factory settings for most parame‐
ters. The following parameter groups are available:
● ALL: Reset all parameters together which can be reset by 'Init',
'PArA' and 'diAg'.
● Init: Reset initialization parameters '1.YFCT' to '5.INITM'.
● PArA: Reset application parameters '6.SCUR' Current range of
setpoint (Page 147) to '49.\\LIM' Response threshold of fault
message 'Control deviation' (Page 159).
● diAg: Resetting the extended diagnostic parameters A to U
(Page 163) as well as parameter '52.XDIAG' Activating for ex‐
tended diagnostics (Page 162).
An overview of the parameters and factory settings can be found in
section Tabular overview of the parameters (Page 135).
In order to select one of the parameter groups listed above, repeat‐
edly press the
button until the desired setting is output in the
display. Start the function by keeping the
'oCAY' is output in the display. The values of the parameter group
are now the factory settings.
If you wish to use a previously initialized positioner on a different
control valve, set the parameters to the factory settings prior to a
new initialization. To do this, use the 'ALL' or 'Init' setting.
Restore the factory settings if you have changed several parameters
at once without being able to predict their effect and the undesired
reactions which may occur as a result. To do this, use the 'ALL'
setting.
ALL
FIP
You have a positioner with the "Fail in place" function with
order suffix -Z, order code F01.
booSt
You operate the positioner with a booster.
Std
Standard pneumatic block
FIP
Fail in place pneumatic block
booSt
Operation with boosters
button pressed until
SIPART PS2 with 4 to 20 mA/HART
Operating Instructions, 11/2019, A5E00074631-AE

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents