Parameter assignment
8.4 Description of parameters
Purpose:
Factory setting:
See also
'1.YFCT' type of actuator (Page 143)
8.4.1.4

'4.INITA' Initialization (automatic)

Possible settings:
Purpose:
Factory setting:
8.4.1.5

'5.INITM' Initialization (manual)

Possible settings:
Purpose:
Description:
Factory setting:
146
Use this parameter to display the determined stroke value in mm
when initialization of a linear actuator has been completed.
If you select the 'OFF' setting, the real stroke is not displayed after
initialization.
From the possible settings shown above, select the value which
corresponds to the range of stroke of your actuator in mm.
If the range of stroke of the actuator does not correspond to a pos‐
sible setting, use the next higher value. Use the value specified on
the nameplate of the actuator for this purpose.
'3.YWAY' is only displayed if '1.YFCT' is set to 'WAY'/'-WAY' or
'ncSLL'/'-ncLL'.
OFF
● NOINI
● no / ###.#
● Strt
Use this parameter to start the automatic initialization process.
1. Select the "Strt" setting.
2. Then press the
button for at least 5 seconds.
The sequence of the initialization process from "RUN 1" to "RUN 5"
is output in the bottom line of the display.
NOINI
● NOINI
● no / ###.#
● Strt
Use this parameter to start the manual initialization process.
1. Select the "Strt" setting.
2. Then press the
button for at least 5 seconds.
If the positioner has already been initialized and if the "4.INITA" and
"5.INITM" values are set, it is possible to reset the positioner to the
non-initialized status. To do this, press the
seconds.
NOINI
button for at least 5
SIPART PS2 with 4 to 20 mA/HART
Operating Instructions, 11/2019, A5E00074631-AE