Siemens SIPART PS2 Series Operating Instructions Manual page 138

Electropneumatic positioners with 4 to 20 ma/hart
Hide thumbs Also See for SIPART PS2 Series:
Table of Contents

Advertisement

Parameter assignment
8.3 Tabular overview of the parameters
Parameter
42.BIN1
43.BIN2
44.AFCT
45.A1
46.A2
47. FCT
48. TIM
49. LIM
138
Function
Digital input function DI1
2)
None
Message only
Block configuration
Block configuring and manual
operation
Move process valve to YE po‐
sition
Move process valve to YA po‐
sition
Block movement
Partial Stroke Test
Digital input function DI2
2)
None
Message only
Move process valve to YE po‐
sition
Move process valve to YA po‐
sition
Block movement
Partial stroke test
Alarm function
3)
None
A1 = Min, A2 = Max
A1 = Min, A2 = Min
A1 = Max, A2 = Max
Response threshold, alarm 1
Response threshold, alarm 2
Function for fault message output
3)
Fault
Fault + not automatic
Fault + not automatic + DI
Monitoring period for setting of fault
message 'Control deviation'
Response threshold of fault message
'Control deviation'
Parameter values
NO contact
on
bLoc1
bLoc2
uP
doWn
StoP
PSt
NO contact
on
uP
doWn
StoP
PSt
Normal
0.0 ... 10.0 ... 100.0
0.0 ... 90.0 ... 100.0
Normal
4)
4)
Auto / 0 ... 100
Auto / 0 ... 100
Operating Instructions, 11/2019, A5E00074631-AE
Unit
NC contact
OFF
-on
-uP
-doWn
-StoP
-PSt
NC contact
OFF
-on
-uP
-doWn
-StoP
-PSt
Inverted
OFF
Inverted
SIPART PS2 with 4 to 20 mA/HART
%
%