Commissioning
7.10 Commissioning linear actuators
4. Set the "3.YWAY" parameter to determine the total stroke in mm. The setting of parameter
3 is optional. The display shows the determined total stroke at the end of the initialization
phase.
– Press the
– Call the "3.YWAY" parameter. To do this, press
5. Call the "4.INITA" parameter. To do this, briefly press the
following:
6. Start the initialization process. To do this, keep the
until the display shows the following:
The positioner runs through five initialization steps during the automatic initialization
process. The displays for the initialization steps from "RUN 1" to "RUN 5" are located in the
lower line of the display. The initialization process depends on the actuator used, and takes
up to 15 minutes.
7. The following display indicates that the automatic initialization is complete:
See also
Sequence of automatic initialization (Page 109)
120
button if you do not require any information about the total stroke in mm.
You then reach parameter 4.
Note
Set the "3.YWAY" parameter
1. On the scale of the lever, read the value marked by the carrier pin.
2. Set the parameter with the buttons
. The display shows the following:
and
to the read value.
button. The display shows the
button pressed for at least 5 seconds
SIPART PS2 with 4 to 20 mA/HART
Operating Instructions, 11/2019, A5E00074631-AE