2. To allow proper heat dissipation, maintain the following minimum clearance areas
between the inverter and other objects:
If installing a single inverter:
20 cm (8") from the top of the inverter.
At least 10 cm (4") from the bottom of the inverter.
10 cm (4") from the right and left of the inverter.
If installing multiple inverters:
When installing inverters side by side, leave at least 20 cm (8") between
inverters.
When installing inverters one above of the other, leave at least 40 cm (16")
between inverters.
3. Position the mounting bracket against the wall/ pole and mark the drilling hole
locations (refer to for inverter and mounting bracket dimensions).
StorEdge Single Phase Inverter with HD-Wave Technology MAN-01-00627-1.1
Chapter 3: Installing the Inverter
Figure 9: Clearance areas
25