Pneumatic Data - Siemens Sipart PS2 6DR5 Series Compact Operating Instructions

Electropneumatic positioners
Hide thumbs Also See for Sipart PS2 6DR5 Series:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
Rated conditions
Degree of protection
1)
Mounting position
Vibration resistance
Harmonic oscillations (sine) according to EN 60068-2-
6/10.2008
Bumping (half-sine) according to EN 60068-2-27/02.2010
Noise (digitally controlled) according to EN 60068-2-
64/04.2009
Recommended range of continuous operation of the entire
control valve
Climate class
Storage
Transport
Max. impact energy 1 Joule for enclosure with inspection window 6DR5..0 and 6DR5..1 or max. 2 Joule for 6DR5..3
1)
At ≤ -10 °C (≤ 14 °F) the display refresh rate of the indicator is limited. When using position feedback module, only T4 is
2)
permissible.
The following applies to order suffix (order code) -Z M40: -40 ... +80 °C (-40 ... +176°F)
3)
7.1.2

Pneumatic data

Pneumatic data
Auxiliary power (air supply)
Pressure
1)
Air quality to ISO 8573-1
Solid particulate size and density
Pressure dew point
Oil content
Unrestricted flow (DIN 1945)
Inlet air valve (ventilate actuator)
2 bar (29 psi)
4 bar (58 psi)
6 bar (87 psi)
Exhaust valve (deaerate actuator for all versions except
fail in place)
2)
2 bar (29 psi)
4 bar (58 psi)
6 bar (87 psi)
Exhaust valve (deaerate actuator for fail in place version)
2 bar (29 psi)
4 bar (58 psi)
6 bar (87 psi)
Valve leakage
Throttle ratio
Auxiliary power consumption in the controlled state
SIPART PS2 (6DR5...)
A5E03436620-AB, 01/2017
2)
IP66 to IEC/EN 60529 / NEMA 4X
Any; in wet environment, pneumatic connections and
outlet opening not upward
3.5 mm (0.14"), 2 ... 27 Hz, 3 cycles/axle
98.1 m/s² (321.84 ft/s²), 27 ... 300 Hz, 3 cycles/axle
150 m/s² (492 ft/s²), 6 ms, 1000 shocks/axle
10 ... 200 Hz; 1 (m/s²)²/Hz (3.28 (ft/s²)²/Hz)
200 ... 500 Hz; 0.3 (m/s²)²/Hz (0.98 (ft/s²)²/Hz)
4 hours/axle
≤ 30 m/s² (98.4 ft/s²) without resonance peak
According to IEC/EN 60721-3
1K5, but -40 ... +80°C (1K5, but -40 ... +176°F)
2K4, but -40 ... +80°C (2K4, but -40 ... +176°F)
Compressed air, carbon dioxide (CO2), nitrogen (N), noble
gases or cleaned natural gas
1.4 ... 7 bar (20.3 to 101.5 psi)
Class 2
Class 2 (min. 20 K (36°F) below ambient temperature)
Class 2
4.1 Nm³/h (18.1 USgpm)
7.1 Nm³/h (31.3 USgpm)
9.8 Nm³/h (43.1 USgpm)
8.2 Nm³/h (36.1 USgpm)
13.7 Nm³/h (60.3 USgpm)
19.2 Nm³/h (84.5 USgpm)
4.3 Nm³/h (19.0 USgpm)
7.3 Nm³/h (32.2 USgpm)
9.8 Nm³/h (43.3 USgpm)
< 6⋅10
Nm³/h (0.0026 USgpm)
-4
Adjustable up to ∞: 1
< 3.6⋅10
Nm³/h (0.158 USgpm)
-2
39