IMPORTANT INVERTER SAFETY INSTRUCTIONS

IMPORTANT INVERTER SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
WARNING!
The inverter cover must be opened only after shutting off the inverter ON/OFF
switch located at the bottom of the Primary Unit, above the Connection Unit.
This disables the DC voltage inside the inverter and opens the AC relays.
Wait five minutes before opening the cover. Otherwise, there is a risk of
electric shock from energy stored in the capacitors.
WARNING!
Before operating the inverter, ensure that the inverter is grounded properly.
WARNING!
Opening the inverter and repairing or testing under power must be performed
only by qualified service personnel familiar with this inverter.
WARNING!
Do not touch the PV panels or any rail system connected when the inverter
switch is ON, unless grounded.
WARNING!
SafeDC complies with IEC60947-3 when installing the system with a worst
case SafeDC voltage (under fault conditions) < 120V.
The worst case voltage is defined as: Voc,max+ (String Length-1)*1V, where:
Voc,max = Maximum Voc (at lowest temperature) of the PV module in
the string (for a string with multiple module models, use the max
value)
String Length = number of power optimizers in the string
CAUTION!
This unit must be operated according to the technical specification datasheet
provided with the unit.
CAUTION!
HEAVY OBJECT. To avoid muscle strain or back injury, use proper lifting
techniques, and if required - a lifting aid.
-Three Phase Inverter with Synergy Technology Installation MAN-01-00402-1.2