Temperatures And Flows; Water Pressure Drop; Fig. 14 - Flow Rate And Pressure Drop Charts - York eco2 YCAS0425EB Installation Operation & Maintenance

Air-cooled screw liquid chillers
Table of Contents

Advertisement

MODEL
LEAVING WATER
TEMPERATURE (°C)
NUMBER
YCAS
MIN.
0425
5.0
0475
5.0
0515
5.0
0555
5.0
0575
5.0
0605
5.0
NOTES:
1. For leaving brine temperature below 4.4°C, contact your nearest YORK office for application requirements.
2. For leaving water temperature higher than 13°C, contact the nearest YORK office for application guidelines.
3. The evaporator is protected against freeze-up to -28.8°C with an electrical heater as standard.
1000
100
10
1
1
0425, 0475, 0515, 0555, 0575, 0605
FIG. 14 – FLOW RATE AND PRESSURE DROP CHARTS
YORK INTERNATIONAL

TEMPERATURES AND FLOWS

1
MAX.
2
13.0
13.0
13.0
13.0
13.0
13.0

WATER PRESSURE DROP

2 CIRCUIT CHILLERS
MODEL NUMBER YCAS
COOLER FLOW
(L/S)
3
MIN.
MAX.
9.5
37.9
10.6
42.3
11.7
46.9
12.4
48.5
13.1
48.5
13.6
48.5
A
10
WATER FLOW (l/s)
COOLER
A
FORM 201.18-NM8
AIR ON
CONDENSER (°C)
MIN.
MAX
-17.7
50
-17.7
50
-17.7
50
-17.7
50
-17.7
50
-17.7
50
LD06966
100
45
7