SolarEdge StorEdge Solution with Backup Installation Manual page 70

Table of Contents

Advertisement

Recommended
cable type
(min-max AWG)
Temperature
sensor terminal
24 AWG (16-24
AWG), 300 Vrms
insulated
Connecting to the Grid and to Backed-up Loads
This section describes:
Connection to the AC Grid.
Connection between the inverter to the backed-up loads panel.
NOTE
If there are multiple inverters in the installation, each inverter should be
connected to a separate backed-up loads panel. Do not share backup output
between inverters.
(1) T1 and T2 are interchangable
StorEdge Solution with Backup MAN-01-00262-1.5
StorEdge
Auto-transformer
Connection Unit
connection
External Devices
Temperature sensor
7-pin terminal
block: T1
External Devices
Temperature sensor
7-pin terminal
block: T2
Chapter 7: StorEdge Inverter Connections
connection
StorEdge Connection
Unit: Press the protrusion
at the top of the terminal
block to open the
connection hole, insert
the wire and release to
(1)
terminal: T1
spring back and clamp
the wire.
Auto-transformer:
 1. Insert a flat blade
terminal: T2
 2. Insert the wire into the
    69
Connection method
screwdriver into the
square opening at the
top of the terminal
block and press to
open clamp
mechanism.
round opening and
release the screwdriver
to spring back and
clamp the wire.