SolarEdge StorEdge Solution with Backup Installation Manual page 62

Table of Contents

Advertisement

The following table, Figure 25 and Figure 26 detail cable types and connections of one
battery (LG-chem Resu10H). Prepare cables and connect as described in the following
table:
StorEdge
Connection Unit
connection
BAT + terminal block
BAT - terminal block
Control and monitoring
5-pin communication
terminal block:
En (Enable)
V+
(1)
B- (RS485)
1
A+ (RS485)
G (RS485)
(1) Must be twisted pair
(2) Must be twisted pair
StorEdge Solution with Backup MAN-01-00262-1.5
LG Chem
Connection method
RESU10H
battery
StorEdge Connection
connection
DC
Insert a flat blade
screwdriver into the
square opening at
DC+
the top of the
terminal block and
press to open clamp
mechanism.
Insert the wire into
the round opening
and release the
DC-
screwdriver to
spring back and
clamp the wire.
 
6-pin connector
Press the protrusion
ENABLE_H
at the top of the
terminal block to
Not connected
open the connection
(2)
hole, insert the wire
RS485_L -
and release to spring
2
RS485_H +
back and clamp the
EN_G
wire.
Chapter 7: StorEdge Inverter Connections
to the
Unit
    61
Recommended cable
type
(min-max AWG)
DC cable 10 AWG (10-
14 AWG), 600V
insulated.
5-wire shielded
twisted pair cable 24
AWG (16-24AWG),
600V insulated.
CAT5 600V insulated
can also be used.