 a. Insert a flat blade screwdriver into the square opening at the top of the terminal
block and press to open clamp mechanism.
 b. Insert the wire into the round opening and release the screwdriver to spring
back and clamp the wire. Check that the wire is fully inserted and cannot be
pulled out easily.
CAUTION!
Ensure that the Plus (+) wire(s) is connected to the (+) terminal and that the
Minus (-) wire is connected to the Minus (-) terminal connector.
 
ATTENTION!
Veillez à ce que le câble(s) Plus (+) soit connecté au terminal (+) et que le
 
câble (-) soit connecté au (-) terminal.
NOTE
For systems with four PV strings per unit or more, fuses
may need to be installed in both the positive and negative
conductors as required by NEC Article 690.9. For more
information, refer to the "String Fusing Requirements
in SolarEdge Systems" technical note at
http://www.solaredge.com/files/pdfs/string_fusing_requirements.pdf

Connecting to the Battery

To simplify the connection process it is advised to connect the battery to the inverter
before mounting the battery according to the manufacturer instructions.
In addition to the manufacturer instructions, follow these guidelines:
Connect and mount the battery as follows:
Connect all the wires to the battery connection panel.
Mount the battery.
Assemble the conduit between the battery and the inverter.
Connect to the StorEdge Connection Unit.
Measure the necessary length between the StorEdge Connection Unit and the
battery for all cables. The maximum distance between the battery and the inverter is
70 ft/ 20 m, when using 24 AWG/ 0.2 mm
StorEdge Solution with Backup MAN-01-00262-1.5
Chapter 7: StorEdge Inverter Connections
2
cables for battery control.
    59
.