  StorEdge Error Codes
Error
Code
Power overload
1Dx31
OFF and ON to resume
Backup init over voltage
1Dx32
Internal CB down
1Dx35
System Warnings
Warnings are displayed in the initial status screen with the format: <Warning X>. For
example:
V a c [ V ] V d c [ V ] P a c [ W ]
1 . 0           0 . 5           0 . 0
P _ O K : X X X / Y Y Y < S _ O K >
W a r n i n g 8                 O N
The warning is a status screen. To view the warning description, press the LCD button.
The following is a list of system warnings:
LCD Message
StorEdge Solution with Backup MAN-01-00262-1.5
Cause and Troubleshooting
Inverter output is overloaded or
output current is higher than
battery max allowed output. The
inverter tried to restart 3 times.
External voltage source on
backed-up loads when
operating in Backup mode.
Disconnect all external voltage
sources on backed-up loads.
Inverter internal error. Contact
SolarEdge support.
Make sure that the loads do not
consume higher current than
the inverter max output current.
Open the inverter StorEdge
Connection Unit and switch the
main circuit breaker to the ON
position.