Code
Connection Unit
1Dx27
Temp. Too High
Meter Comm. Error
1Dx2D
Battery Comm Error
1Dx2E
StorEdge Solution with Backup MAN-01-00262-1.5
LCD Message
Appendix A: Troubleshooting
Cause and Troubleshooting
digital board in the inverter.
Check that the StorEdge
Connection Unit LEDs are ON.
Inverter production stopped due
to StorEdge Connection Unit
overheating or due to internal
fan malfunction.
Clean the StorEdge Connection
Unit fan
If the fan is malfunctioning,
replace the fan
Refer to Troubleshooting on
page 123.
Check the wiring to the battery
and the battery DIP switch
configuration (refer to
Connecting to the Battery on
page 59 and DIP Switch Setup
on page 64).
Connecting to the Battery on
page 59
Check the battery setup in the
RS485-Conf screen (refer to
Configuring the RS485 Bus for
Battery and Meter Connection
on page 111).