SolarEdge StorEdge Solution with Backup Installation Manual page 132

Table of Contents

Advertisement

Problem
displayed
The inverter does not turn
on.
A battery internal fault is
displayed on the
LCD:Battery Internal Fault
XXXX (ID: XX)
Battery self test failed. One
of the following messages
is displayed for BAT 1 or
BAT 2 (if applicable):
N/A / FAILED /
FAILED CHARGE /
FAILED DISCHARGE
 
StorEdge Solution with Backup MAN-01-00262-1.5
Description or Possible
Cause
The short circuit jumper
has been removed from
the external devices
terminal block, but no
external shutdown switch
has been connected.
The external shutdown
switch (if connected) is in
the Off position.
Fault # –according to
battery model. ID –
battery's Modbus ID.
N/A - battery not tested.
FAILED - both charge
and discharge failed.
FAILED CHARGE /
FAILED DISCHARGE -
one of these functions
failed.
Appendix A: Troubleshooting
Troubleshooting
Reconnect the short circuit
jumper or make sure the
external shutdown switch is
properly connected (see
"External Rapid Shutdown"
on page 143).
Turn on the external
shutdown switch (see
"External Rapid Shutdown"
on page 143).
Contact SolarEdge Support
Check the battery
connections.