SolarEdge StorEdge Solution with Backup Installation Manual page 119

Table of Contents

Advertisement

118
  Configuring StorEdge Applications
B a c k u p R s v d < 2 0 % >
G r i d C h a r g e < E n >
A C C h a r g e L i < N o n e >
 c. Select Grid Charge and one of the following options:
Enable: Charge from both PV and grid to reach backup reserved value
Disable: Charge from PV only to reach backup reserved value
Setting Charge/ Discharge Profile + Backup Power
In this mode, you first set the system to charge/ discharge profile (for time-of-use
arbitrage) and the level of charging the battery from AC. Then, you set up the level of
stored energy to be reserved for backup.
To set up Charge/ Discharge Profile (TOU) + Backup Power:
 1. Access the Energy Ctrl. menu as described above.
 2. Select Time of Use.The Energy Manager screen changes to display the following:
L i m i t C o n t r o l < D i s >
E n e r g y C t r l < T O U >
S e t C a l e n d a r
S t o r a g e C o n t r o l
 3. From the Energy Manager menu select Set Calendar. The following screen is
displayed, showing options for calendar setting:
S e r v e r S y n c < D i s >
L o a d S D < N / A >
 
 4. Do one of the following:
To load a time-of-use table from the monitoring platform, refer to
https://www.solaredge.us/sites/default/files/storedge_charge_discharge_
profile_programming.pdf
To load a time-of-use table from the SolarEdge SD card (contact SolarEdge to
obtain it), insert the card to the slot labeled "Card" on the communication board
and select Load SD. From the displayed list select the directory and the table
(filename).
 5. To set up the level of charging from AC, do the following:
 a. Select Energy Manager è Storage Control. The following is displayed:
B a c k u p R s v d < N / A >
A C C h a r g e L i < N o n e >
 
.
StorEdge Solution with Backup MAN-01-00262-1.5