SolarEdge StorEdge Solution with Backup Installation Manual page 103

Table of Contents

Advertisement

102
  Creating an Ethernet (LAN) Connection
To connect the Ethernet cable:
 1. Remove the inverter cover as described in Removing the Inverter Cover on page 45.
 2. Open the communication gland #1.
CAUTION!
The gland includes a rubber waterproof fitting, which should be used to
ensure proper sealing.
 
ATTENTION!
Le cote interne du gland contient une rondelle qui doit être utilisée pour
 
une bonne étancheïté.
 3. Remove the plastic seal from one of the large opening .
 4. Remove the rubber fitting from the gland and insert the CAT5/6 cable through the
gland and through the gland opening in the inverter
 5. Push the cable into the cut opening of the rubber fitting.
CAT5/6 standard cables have eight wires (four twisted pairs), as shown in the diagram
below. Wire colors may differ from one cable to another. You can use either wiring
standard, as long as both sides of the cable have the same pin-out and color-coding.
RJ45 Pin #
1
White/Orange
2
Orange
3
White/Green
4
Blue
5
White/Blue
6
Green
7
White/Brown
8
Brown
(1) The inverter connection does not support RX/TX polarity change. Supporting crossover Ethernet cables depends on
the switch capabilities.
Figure 36: Rubber fitting
(1)
Wire Color
T568B
White/Green
White/Orange
White/Brown
T568A
Transmit+
Green
Transmit-
Receive+
Blue
Reserved
White/Blue
Reserved
Orange
Received-
Reserved
Brown
Reserved
StorEdge Solution with Backup MAN-01-00262-1.5