→ Alarm display
→ Time activation
→ Time safety
16.3

Special remarks

If the value 2 (BDE-M/4-positions) has been programmed and an external mechanical BDE
(BDE-M) has been connected, the inputs (BDE1, BDE2) will be interpreted in a different
manner. On the circuit board in the mounting set, BDI-M DFA 127 (102-127808232) is
equipped with clamps that permit the external adjustment of the operation mode according
to the table below.
Terminal connections on the circuit board in the mounting set BDI-M:
102-127108955
In this menu, some error messages can be adapted to special
requirements.
▪ Display for AKI/AKA/SSK or SIO/SIS
18
Triggering signals activated for a relatively long time (AKI,
AKA, SSK) are displayed with an error message.
0 = no error message
1..40 = display an error message after 5..200 seconds
18
Safety signals activated for a relatively long time (SIO, SIS)
are displayed with an error message.
0 = no error message
1..40 = display an error message after 5..200 seconds
Input/output on
STG DFA 127
BDE 1
BDE 2
+ 24 V
NOTICE
If using the circuit board on the side cover, only the RESET button and the status
signal remain in function.
If the alarm output has been configured, it switches
after expiry of the set time.
Clamps on
STG DFA 127
J7/1
J7/2
J7/3
V1.1
Configurations
Clamp marking on BDI-
M
1
2
3
16
80/ 102