Additional Requirements; General And Additional Requirements; Detection Zone For Sensor Activation - Record DFA127 Instructions Manual

Automatic door systems
Hide thumbs Also See for DFA127:
Table of Contents

Advertisement

3.1.7

Additional requirements

Opening time
Doorsets shall open from closed to back check, or 80° whichever occurs first, in 3 s or longer
as required in the table below.
Closing time
The minimum closing time from 90° to 10° open (+ min. 1.5 s from 10° to 0°) shall be ad-
justed on site according to the table below. The times are to be checked with an appropriate
measuring device (e.g. stop watch).
Width of door-
set leaf
(m)
0,75
0,85
1,00
1,20
Note: Values for time are rounded up to the nearest half second.
3.2

General and additional requirements

3.2.1

Detection zone for sensor activation

Attention shall be paid to the provision and positioning of sufficient automatic activation de-
vices (sensors) for different types of doorset.
In the case of power-operated doorsets on escape routes without break-out function, the de-
tection zone in the escape direction shall be not less than 1500 mm measured from the cen-
tre of the opening width of the doorset - and if possible 1000 mm for all other doors. The de-
tection zone shall cover at least the entire opening width of the doorset.
Solution:
Sensors must be set correctly during commissioning.
On escape routes and emergency exits, a combined sensor RIC 290 must be installed on
the inner side.
102-127108955
Security inspection according EN 16005
50
60
3,0
3,0
3,0
3,0
3,5
3,5
4,0
4,5
CAUTION
A combined sensor AIR 290 does not meet the 1500 mm requirement and is
consequently not allowed.
V1.1
Mass of doorset leaf (kg)
70
Time (s)
3,0
3,5
4,0
4,5
80
90
3,0
3,5
3,5
4,0
4,0
4,5
5,0
5,5
18/ 102
3