1.7 ELECTRIC CONNECTION.

The appliance has an IPX4D degree of protection;
electrical safety of the appliance is achieved only
when it is properly connected to an efficient
earthing system, as specified by current safety
standards.
Attention: Immergas S.p.A. declines any respon-
sibility for damage or physical injury caused by
failure to connect the hydronic module to an
efficient earthing system or failure to comply
with the reference standards.
- Connection cables must respect the prear-
ranged routes. Use 3 clips (c) (not supplied)
to group the individual cables (max. 1.5 mm
into the lower terminal board. Use the specific
fairleads (d) on the left side, making sure to put
at most 2 multi-polar cables (max 3 x 1 mm
in each fairlead.
As an example, figure 1-5 shows cables in a
hypothetical connection. To make the connec-
tions based on your own requirements, see the
instructions below.
• Open the control panel connections compart-
ment (Fig. 1-5).
To carry out electrical connections, all you have
to do is open the connections compartment as
follows.
- Remove the front panel (Fig. 3-5b).
- Remove the cover (b fig. 1-4).
1) Loosen the screws (a).
2) Remove the cover (b) from the control
panel (c).
- At this point, you can access the terminal board.
Also ensure that the electrical installation corre-
sponds to the maximum absorbed power speci-
1-5
COM.
CLOSED
2
)
2
d
1-4
OPEN
DHW
DIS. AUDAX PRO
c
a
1
a
Key:
86 /87 - Summer winter switch 3-way valve
81-2 / 82-2 - Zone 2 circulator
83-2 / 84-2 / 85-2 - Zone 2 mixing valve
82-1 / 81-1 - Zone 1 circulator
89 / L - Audax Pro disabling contact
88 / L - Solar inlet
69 / 70 - Domestic hot water integrated resistance control
38 / 39 - External Probe
37 / 38 - Domestic hot water probe (eliminate R8)
42-1 / 43 - Zone 1 CAR
42-2 / 43 - Zone 2 CAR
23-1 / 24 - Zone 1 humidistat or humidity probe
23-2 / 24 - Zone 2 humidistat or humidity probe
25 - Humidity sensor supply voltage
29-1 / 30-1 - Zone 1 dehumidifier
29-2 / 30-2 - Zone 2 dehumidifier
T+ / T- (MC) - Audax Pro communication bus
T+ / T- (RS485) - Other Immergas appliance communication
bus
41-1 / 40-1 - Zone 1 room thermostat
41-2 / 40-2 - Zone 2 room thermostat
66 / 65 - Puffer central heating probe
65 / 64-2 - Zone 2 flow probe
8
c
1
1
2
1
a
b
a
V2
V2