Technical Data - Immergas MAGIS PRO ERP Instruction And Recommendation Booklet

Mono-phase hydronic module to pair with an outdoor condensing unit
Table of Contents

Advertisement

3.16 TECHNICAL DATA.

The data below refer to the pairing between
hydronic module and Audax Pro.
Nominal data for low temperature applications *
Nominal central heating output
Absorption
COP
Nominal cooling output
Absorption
EER
Nominal output for average temperature applications **
Nominal central heating output
Absorption
COP
Nominal cooling output
Absorption
EER
Nominal output for high temperature applications **
Nominal central heating output
Absorption
COP
* Central heating mode status: heat exchanger water inlet/remains at 30 °C/35 °C, outdoor air temperature 7 °C db/6 °C wb. Performance in compliance
with EN 14511.
Cooling mode status: heat exchanger water inlet/remains at 23 °C/18 °C, outdoor air temperature 35 °C. Performance in compliance with EN 14511.
** Central heating mode status: heat exchanger water inlet/remains at 40 °C/45 °C, outdoor air temperature 7 °C db/6 °C wb.
Cooling mode status: heat exchanger water inlet/remains at 12 °C/7 °C, outdoor air temperature 35 °C. Performance in compliance with EN 14511.
*** Central heating mode status: inlet/remains at 47 °C/55 °C, outdoor air temperature 7 °C db/6 °C wb. Performance in compliance with EN 14511.
Hydronic module data.
Hydraulic circuit max. operating pressure
Maximum central heating temperature
Adjustable central heating temperature (max operating field)
Head available with 1000 l/h flow rate
Domestic hot water adjustable temperature
Water content
Expansion vessel volume
Expansion vessel factory-set pressure
Hydraulic circuit maximum pressure
Electrical connection
Absorption without additional loads
Maximum absorption with loads
Integrated resistance absorption (optional)
EEI value
Equipment electrical system protection
Empty hydronic unit weight
Full hydronic unit weight
Magis Pro 5 ErP
kW
5.80
kW
1.28
kW/kW
4.53
kW
6.03
kW
1.67
kW/kW
3.61
kW
5.30
kW
1.55
kW/kW
3.42
kW
4.90
kW
1.87
kW/kW
2.62
kW
4.80
kW
1.82
kW/kW
2.64
kPa (m c.a.)
V/Hz
31
Magis Pro 8 ErP
Magis Pro 10 ErP
7.71
9.80
1.89
2.39
4.08
4.10
7.58
7.58
2.01
2.01
3.77
3.77
7.26
9.27
2.32
2.98
3.13
3.11
5.38
7.31
2.26
3.07
2.38
2.38
6.17
8.45
2.64
3.59
2.34
2.35
bar
3
°C
70
°C
25 - 55
44.2 (4.5)
°C
30 - 65
l
4.0
l
12.0
bar
1.0
kPa
300
230 / 50
W
65
W
170
kW
3
-
≤ 0.20 - Part. 3
-
IPX4D
kg
33.5
kg
37.5

Hide quick links: