Heat regulation menu.
Id
Parameter
Parameter
Defines if and which external probe is used to manage the system.
OFF = no external probe used
R 01
External probe
OU = external probe on the condensing unit
IU = optional external probe connected to the hydronic module
Outdoor temper-
Establishes the outdoor temperature at which to have the maximum flow
R 02
ature for max CH
temperature.
flow
Outdoor temper-
Establishes the outdoor temperature at which to have the minimum flow
R 03
ature for min CH
temperature.
flow
Maximum cen-
R 04
Defines the maximum flow temperature in room central heating mode
tral heating
Minimum central
R 05
Defines the minimum flow temperature in room central heating mode
heating
Outdoor tem-
perature for low
Establishes the outdoor temperature at which to have the maximum flow
R 06
temperature zone
temperature in the low temperature zone
max CH flow
Outdoor tem-
perature for low
Establishes the outdoor temperature at which to have the minimum flow
R 07
temperature zone
temperature in the low temperature zone
min CH flow
Low temperature
Defines the maximum flow temperature in room central heating mode in
R 08
zone maximum
the low temperature zone
central heating
Low temperature
Defines the minimum flow temperature in room central heating mode in
R 09
zone minimum
the low temperature zone
central heating
Outdoor
temperature
Establishes the maximum outdoor temperature at which to have the mini-
R 10
for minimum
mum flow temperature in cooling mode
cooling flow
Outdoor
temperature
Establishes the minimum outdoor temperature at which to have the maxi-
R 11
for maximum
mum flow temperature in cooling mode
cooling flow
Minimum
R 12
Defines the minimum flow temperature in room cooling mode
cooling
Maximum
R 13
Defines the maximum flow temperature in room cooling mode
cooling
Outdoor
temperature for
Establishes the outdoor temperature at which to have the minimum flow
R 14
low temperature
temperature in the low temperature zone
zone minimum
cooling flow
Outdoor tem-
perature for low
Establishes the outdoor temperature at which to have the maximum flow
R 15
temperature zone
temperature in the low temperature zone
max cooling flow
Low temperature
Defines the minimum flow temperature in room cooling mode in the low
R 16
zone minimum
temperature zone
cooling
Low temperature
Defines the maximum flow temperature in room cooling mode in the low
R 17
zone maximum
temperature zone
cooling
Description
26
Customised
Range
Default
value
OFF - OU
OU
- IU
-15 ÷ 25 °C
-5
-15 ÷ 25 °C
25
35 ÷ 55
45
25 ÷ 55
25
-15 ÷ 25 °C
-5
-15 ÷ 25 °C
25
35 ÷ 55
35
25 ÷ 35
25
20 ÷ 40
35
20 ÷ 40
25
07 ÷ 20
7
10 ÷ 25
12
20 ÷ 40
35
20 ÷ 40
25
07 ÷ 20
18
10 ÷ 25
20