Non-Contacting Position Sensor - Siemens SIPART PS2 Compact Operating Instructions

Electropneumatic positioners
Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
7.5.6

Non-contacting position sensor

Additional modules
Actuating range
● Linear actuator 6DR4004-.N.20
● Linear actuator 6DR4004-.N.30
● Part-turn actuator
Linearity (after corrections made by
positioner)
Hysteresis
Temperature influence (range:
rotation angle 120° or stroke
14 mm)
Climate class
● Storage
● Transportation
Vibration resistance
● Harmonic oscillations
(sine wave) according to
IEC 60068-2-6
● Permanent shocks according to
IEC 60068-2-29
Torque for cable gland nut made of
Housing protection type
For connecting to circuits with the
following peak values
Certificates and approvals
CE conformity
Explosion protection
Types of protection
● Intrinsic safety "ia"
● Intrinsic safety "ic"
● Non-sparking "nA"
Permissible ambient temperature
46
Without explosion protection
10 ... 130 mm (0.39 ... 5.12"); up to 200 mm (7.87") on request
≤ 0.1%/10 K (≤ 0.1%/18 °F) for -20 to 90 °C (-4 to 194 °F)
≤ 0.2%/10 K (≤ 0.2%/18 °F) for -40 to -20 °C (-40 to -4 °F)
1K5, but -40 to +90 °C (1K5, but -40 to +176 °F)
2K4, but -40 to +90 °C (2K4, but -40 to +176 °F)
3.5 mm (0.14"), 2 ... 27 Hz, 3 cycles/axis
98.1 m/s² (321.84 ft/s²), 27 ... 300 Hz, 3 cycles/axis
300 m/s
Plastic
2.5 Nm (1.8 ft lb)
IP68 according to EN 60529; NEMA 4X / Encl. Type 4X
-
The applicable directives and standards applied with their revision levels can be
found in the EC declaration of conformity on the Internet.
Ex markings
ATEX/IECEx
Zone 1:
II 2 G Ex ia IIC T6/T4 Gb
Zone 2:
II 3 G Ex ic IIC T6/T4 Gc
Zone 2:
II 3 G Ex nA IIC T6/T4 Gc
T4: -40 ... +90 °C (-40 ... +194 °F)
T6: -40 ... +70 °C (-40 ... +158 °F)
With Ex protection
Ex "ia"
3 to 14 mm (0.12 ... 0.55")
30 ... 100°
± 1 %
± 0.2%
According to DIN EN 60721-3-4
(984 ft/s
), 6 ms, 4000 shocks/axis
2
2
Metal
4.2 Nm (3.1 ft lb)
U
= 5 V
i
C
= 180 nF
i
L
= 922 μH
i
I
= 160 mA
i
P
= 120 mW
i
FM
IS, Class I, Divison 1, ABCD
IS, Class I, Zone 1, AEx ib, IIC
-
NI, Class I, Divison 2, ABCD
NI, Class I, Zone 2, AEx nA, IIC
T4: -40 ... +85 °C (-40 ... +185 °F)
T6: -40 ... +70 °C (-40 ... +158 °F)
With Ex protection
Ex "ic", "nA"
Stainless steel
4.2 Nm (3.1 ft lb)
U
= 5 V
i
C
= 180 nF
i
L
= 922 μH
i
SIPART PS2 (6DR5...)
A5E03436683-02, 01/2013