5.2 Electrical wiring
Procedure for device versions with flameproof enclosure "Ex d"
Figure 5-5
1. Strip the bus cable.
2. Open the safety catch and unscrew the screw cap to open the positioner.
3. Insert the prepared bus cable
certified cable inlet
system.
4. Fasten the shield on the adapter using the clamp
5. Tighten the Ex d-certified cable inlet
6. Connect the red and the green wires to terminals 6 and 7 of the basic electronics as shown
in the following picture. The polarity does not play any role here.
If a bus connection is not present, connect a separate power source with the following values
to terminals 6/7:
● With intrinsically-safe devices: intrinsically-safe isolating power supply with 24 V DC
● With non-intrinsically-safe devices: 15 to 30 V DC
Then match the positioner to the respective actuator by configuring and initializing it. Finally set
the bus address.
84
Basic electronics bus cable
Grounding terminal
Ex d certified cable inlet
Bus cable
Cable clamp/shield
Connection of bus cable for versions with flameproof enclosure
. Follow the corresponding guidelines if you are using a conduit piping
(described in Bus cable (Page 82)) through the Ex d-
and the two screws.
.